Plan Review Notes For Permit 15080661
Permit Number 15080661
Review Stop B
Sequence Number 2
Notes
Date Text
2015-09-18 13:34:34****CORRECTIONS****
 COURTESY REVIEW - SCOPE CLARIFIED
 A DCA APPROVED MANUFACTURED BUILDING IS PROPOSED, WITH
 MODIFICATIONS
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. BASED ON THE SITE PLAN PROVIDED, IT APPEARS THAT THE
 PROPOSED LOCATION FOR THIS SALES TRAILER IS 4847 FRED
 GLADSTONE DRIVE. SUBMIT A CHANGE OF ADDRESS THROUGH THE
 FRONT COUNTER OR REVISE THE SITE PLAN TO SHOW THE
 PROPOSED SALES TRAILER RELATIVE TO THE LOT LINES, FBC
 107.
  
 2. FS 553.80, PROVIDE THE STATE APPROVED PLANS AND
 STATE APPROVAL COVER SHEET WHICH SHOWS THE APPROVAL
 NUMBER. THIS SHOULD BE ON THE INSIGNIA.
  
 ADVISORY ONLY, PLANS PREPARED BY REBECCA M. GATES WERE
 NOT YET REVIEWED BY FIRE (FIRE HAD PLANS CHECKED OUT
 WHEN THESE SHEETS WERE SUBMITTED) BUT WILL BE REVIEWED
 WHEN PLANS ARE RESUBMITTED.
  
 PERMIT WILL BE ISSUED WITH PROVISO THAT, UPON BUILDING
 INSPECTION, THE DCA/DBPR INSIGNIA WILL BE REMOVED AND
 RETURNED TO DBPR.
  
 REVISE PLANS PREPARED BY REBECCA M. GATES TO INCLUDE
 GOVERNING CODE.
  
 IN ADDITION TO THE CHANGE IN FLOOR PLAN, IT APPEARS
 THAT A DOOR HAS BEEN ELIMINATED AND A WINDOW IS
 PROPOSED, BUT NO DETAIL WAS PROVIDED. PROVIDE A
 STRUCTURAL DETAIL AND INCLUDE WIND DESIGN CRITERIA FBC
 1603.1.4. A PRODUCT APPROVAL REVIEWED BY DESIGNER OF
 RECORD REQUIRED.
  
 3. PER ATCOUNCIL.ORG, THIS LOCATION IS RISK CATEGORY II
 167 MPH. PLANS SUBMITTED ARE LIMITED TO 165 MPH, SEE
 SHEET C1, FBC 1609. PER THE STATE OF FLORIDA, IF AN
 EXISTING MANUFACTURED (MODULAR) BUILDING IS MOVVED TO A
 NEW LOCATION, THE RELOCATED BUILDING SHALL COMPLY WITH
 THE WIND SPEED OF THE NEW LOCATION.
  
 THE MANUFACTURED BUILDING PLANS AS SUBMITTED DO NOT
 COMPLY WITH THE WIND SPEED REQUIREMENT FOR THE
 LOCATION. PLEASE ADDRESS, EITHER BY PROVIDING A NEW
 MANUFACTURED BUILDING WHICH COMPLIES WITH 167MPH WIND
 SPEED, OR BY PROVIDING ENGINEERING TO INCREASE THE
 LIMITATION FOR THE BUILDING PROPOSED FROM 165MPH TO
 167MPH.
  
 4. SHOW 18 IN MANEUVERING CLEARANCE FOR DOORS, PULL
 SIDE, FBC ACCESSIBILITY 404.2.4.1, ROOMS 4 AND 5.
  
 5. DETAIL 3 SK5, SEAT HEIGHT NOT CLEAR, FBC 5TH ED
 ACCESSIBILITY 604.4, PLEASE REVISE TO CLARIFY. DETAIL 2
 SK5, PROVIDE LAV HEIGHT AND KNEE CLEARANCE, 606.3.
  
 5. STAIR, RAMP, LANDING, RAILING DETAILS NOT PROVIDED,
 FBC CHAPTER 10, FBC ACCESSIBILITY.
  
 6. SHEET SP1 SHOWS 38.8 FT FROM PROPOSED SALES OFFICE
 TO EXISTING RESNICK BUILDING. REVISE TO SHOW ASSUMED
 PROPERTY LINE BETWEEN THE TWO BUILDINGS, FBC 705.3 AND
 SHOW COMPLIANCE WITH FBC TABLES 602, 705.8.
  
 7. FOR IMPACT FEES, EITHER:
  
 A. PROVIDE THE REMOVAL AGREEMENT WHEREIN OWNER AGREES
 THAT THE PROPOSED TEMPORARY SALES TRAILER WILL BE
 REMOVED BY A CERTAIN DATE (PER WILLIE SWOPE), OR
  
 B. AN IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS
 REQUIRED. 561-233-5025 FOR MORE INFORMATION; PROVIDE
 THE STAMPED PLAN AND RECEIPT SHOWING FEES WERE PAID, IF
 APPLICABLE.
  
 IF CONTRACTOR DOES NOT UNDERSTAND ITEM A, TAKE PLANS TO
 PALM BEACH COUNTY FOR IMPACT FEE ASSESSMENT.
  
 8. IMPACT PROTECTION REQUIRED, SEE SITE INSTALLED
 ITEMS, FBC 1609.1.4. IF SHUTTERS ARE PROPOSED, PROVIDE
 THE PRODUCT APPROVAL AND COMPLETE THE SAMPLE
 INSTALLATION SCHEDULE:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
 THIS CAN BE A PROVISO ITEM, SEPARATE PERMIT REQUIRED.
  
 9. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF PLANS FOR PERMIT ISSUANCE. OLD SHEETS SHOULD BE
 MARKED "VOID" AND LEFT IN THE PERMIT APPLICATION
 PACKAGE.
  
  
  