2015-09-18 13:34:34 | ****CORRECTIONS**** |
| COURTESY REVIEW - SCOPE CLARIFIED |
| A DCA APPROVED MANUFACTURED BUILDING IS PROPOSED, WITH |
| MODIFICATIONS |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. BASED ON THE SITE PLAN PROVIDED, IT APPEARS THAT THE |
| PROPOSED LOCATION FOR THIS SALES TRAILER IS 4847 FRED |
| GLADSTONE DRIVE. SUBMIT A CHANGE OF ADDRESS THROUGH THE |
| FRONT COUNTER OR REVISE THE SITE PLAN TO SHOW THE |
| PROPOSED SALES TRAILER RELATIVE TO THE LOT LINES, FBC |
| 107. |
| |
| 2. FS 553.80, PROVIDE THE STATE APPROVED PLANS AND |
| STATE APPROVAL COVER SHEET WHICH SHOWS THE APPROVAL |
| NUMBER. THIS SHOULD BE ON THE INSIGNIA. |
| |
| ADVISORY ONLY, PLANS PREPARED BY REBECCA M. GATES WERE |
| NOT YET REVIEWED BY FIRE (FIRE HAD PLANS CHECKED OUT |
| WHEN THESE SHEETS WERE SUBMITTED) BUT WILL BE REVIEWED |
| WHEN PLANS ARE RESUBMITTED. |
| |
| PERMIT WILL BE ISSUED WITH PROVISO THAT, UPON BUILDING |
| INSPECTION, THE DCA/DBPR INSIGNIA WILL BE REMOVED AND |
| RETURNED TO DBPR. |
| |
| REVISE PLANS PREPARED BY REBECCA M. GATES TO INCLUDE |
| GOVERNING CODE. |
| |
| IN ADDITION TO THE CHANGE IN FLOOR PLAN, IT APPEARS |
| THAT A DOOR HAS BEEN ELIMINATED AND A WINDOW IS |
| PROPOSED, BUT NO DETAIL WAS PROVIDED. PROVIDE A |
| STRUCTURAL DETAIL AND INCLUDE WIND DESIGN CRITERIA FBC |
| 1603.1.4. A PRODUCT APPROVAL REVIEWED BY DESIGNER OF |
| RECORD REQUIRED. |
| |
| 3. PER ATCOUNCIL.ORG, THIS LOCATION IS RISK CATEGORY II |
| 167 MPH. PLANS SUBMITTED ARE LIMITED TO 165 MPH, SEE |
| SHEET C1, FBC 1609. PER THE STATE OF FLORIDA, IF AN |
| EXISTING MANUFACTURED (MODULAR) BUILDING IS MOVVED TO A |
| NEW LOCATION, THE RELOCATED BUILDING SHALL COMPLY WITH |
| THE WIND SPEED OF THE NEW LOCATION. |
| |
| THE MANUFACTURED BUILDING PLANS AS SUBMITTED DO NOT |
| COMPLY WITH THE WIND SPEED REQUIREMENT FOR THE |
| LOCATION. PLEASE ADDRESS, EITHER BY PROVIDING A NEW |
| MANUFACTURED BUILDING WHICH COMPLIES WITH 167MPH WIND |
| SPEED, OR BY PROVIDING ENGINEERING TO INCREASE THE |
| LIMITATION FOR THE BUILDING PROPOSED FROM 165MPH TO |
| 167MPH. |
| |
| 4. SHOW 18 IN MANEUVERING CLEARANCE FOR DOORS, PULL |
| SIDE, FBC ACCESSIBILITY 404.2.4.1, ROOMS 4 AND 5. |
| |
| 5. DETAIL 3 SK5, SEAT HEIGHT NOT CLEAR, FBC 5TH ED |
| ACCESSIBILITY 604.4, PLEASE REVISE TO CLARIFY. DETAIL 2 |
| SK5, PROVIDE LAV HEIGHT AND KNEE CLEARANCE, 606.3. |
| |
| 5. STAIR, RAMP, LANDING, RAILING DETAILS NOT PROVIDED, |
| FBC CHAPTER 10, FBC ACCESSIBILITY. |
| |
| 6. SHEET SP1 SHOWS 38.8 FT FROM PROPOSED SALES OFFICE |
| TO EXISTING RESNICK BUILDING. REVISE TO SHOW ASSUMED |
| PROPERTY LINE BETWEEN THE TWO BUILDINGS, FBC 705.3 AND |
| SHOW COMPLIANCE WITH FBC TABLES 602, 705.8. |
| |
| 7. FOR IMPACT FEES, EITHER: |
| |
| A. PROVIDE THE REMOVAL AGREEMENT WHEREIN OWNER AGREES |
| THAT THE PROPOSED TEMPORARY SALES TRAILER WILL BE |
| REMOVED BY A CERTAIN DATE (PER WILLIE SWOPE), OR |
| |
| B. AN IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY IS |
| REQUIRED. 561-233-5025 FOR MORE INFORMATION; PROVIDE |
| THE STAMPED PLAN AND RECEIPT SHOWING FEES WERE PAID, IF |
| APPLICABLE. |
| |
| IF CONTRACTOR DOES NOT UNDERSTAND ITEM A, TAKE PLANS TO |
| PALM BEACH COUNTY FOR IMPACT FEE ASSESSMENT. |
| |
| 8. IMPACT PROTECTION REQUIRED, SEE SITE INSTALLED |
| ITEMS, FBC 1609.1.4. IF SHUTTERS ARE PROPOSED, PROVIDE |
| THE PRODUCT APPROVAL AND COMPLETE THE SAMPLE |
| INSTALLATION SCHEDULE: |
| |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/SCHEDULE_FOR_INSTALLATION.PDF |
| |
| THIS CAN BE A PROVISO ITEM, SEPARATE PERMIT REQUIRED. |
| |
| 9. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED |
| SETS OF PLANS FOR PERMIT ISSUANCE. OLD SHEETS SHOULD BE |
| MARKED "VOID" AND LEFT IN THE PERMIT APPLICATION |
| PACKAGE. |
| |
| |
| |