Plan Review Notes
Plan Review Notes For Permit 15080661
Permit Number 15080661
Review Stop P
Sequence Number 1
Notes
Date Text
2015-09-03 06:06:161) PLEASE BIND ALL THE PLANS INTO TWO COMPLETE SETS FOR
 REVIEW.
 2) SHT. SK-2 THE STAFF ROOM SINK SHALL COMPLY WITH THE
 FBC-ACCESSIBILITY SEC.212.1, 606.
 3) SHT. SK-5 - SHOW THE HEIGHT OF THE WATER CLOSET TO
 THE TOP OF THE SEAT. COMPLY WITH 2014 FBC-ACCESSIBILITY
 SEC. 604.4.
 4) SHT. SK-5 - SHOW THE DIMENSIONSTO THE BOTTOM & TOP
 OF THE LAVATORY FROM THE FINISH FLOOR. COMPLY WITH 2014
 FBC-ACCESSIBILITY SECS.606.2,606.3.
 5) SHOW THE DIMENSIONS OF THE TOILET ROOM ON THE PLANS.
 WPB AMEND. TO FBC SEC. 107.2.1.
 6) SHT.P0.1 - A BACKFLOW PREVENTION DEVICE SHALL BE
 INSTALLED ON THE WATER SERVICE PER FBC-P SEC.608.1
 7) THE FLOOR PLAN ON THE SK DRAWINGS DOES NOT CORRELATE
 WITH THE FLOOR PLAN OF THE MODULAR BUILDING.CLARIFY.
 8) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FFOR THE
 EEMAX WATER HEATER. WPB AMEND. TO FBC SEC. 107.2.1.
 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER
 COOLER.WPB AMEND. TO FBC SEC. 107.2.1.
 10) SHOW THE LOCATION OF THE WATER COOLER ON THE FLOOR
 PLAN.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  