Plan Review Notes For Permit 15080661 |
Permit Number |
15080661 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-09-03 06:06:16 | 1) PLEASE BIND ALL THE PLANS INTO TWO COMPLETE SETS FOR | | REVIEW. | | 2) SHT. SK-2 THE STAFF ROOM SINK SHALL COMPLY WITH THE | | FBC-ACCESSIBILITY SEC.212.1, 606. | | 3) SHT. SK-5 - SHOW THE HEIGHT OF THE WATER CLOSET TO | | THE TOP OF THE SEAT. COMPLY WITH 2014 FBC-ACCESSIBILITY | | SEC. 604.4. | | 4) SHT. SK-5 - SHOW THE DIMENSIONSTO THE BOTTOM & TOP | | OF THE LAVATORY FROM THE FINISH FLOOR. COMPLY WITH 2014 | | FBC-ACCESSIBILITY SECS.606.2,606.3. | | 5) SHOW THE DIMENSIONS OF THE TOILET ROOM ON THE PLANS. | | WPB AMEND. TO FBC SEC. 107.2.1. | | 6) SHT.P0.1 - A BACKFLOW PREVENTION DEVICE SHALL BE | | INSTALLED ON THE WATER SERVICE PER FBC-P SEC.608.1 | | 7) THE FLOOR PLAN ON THE SK DRAWINGS DOES NOT CORRELATE | | WITH THE FLOOR PLAN OF THE MODULAR BUILDING.CLARIFY. | | 8) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FFOR THE | | EEMAX WATER HEATER. WPB AMEND. TO FBC SEC. 107.2.1. | | 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER | | COOLER.WPB AMEND. TO FBC SEC. 107.2.1. | | 10) SHOW THE LOCATION OF THE WATER COOLER ON THE FLOOR | | PLAN. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|