Date |
Text |
2015-11-05 09:21:40 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| CONSIDER THE PREVIOUS COMMENTS AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
2015-08-26 09:18:10 | 8/26/2015 PASSED WITH PROVISO: |
| |
| 1. PER NFPA 241- STANDARD FOR SAFEGUARDING |
| CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS, |
| SECTION 4.2 TEMPORARY CONSTRUCTION TRAILERS SHALL BE |
| SEPARATED FROM ADJACENT TRAILERS OR STRUCTURES IN |
| ACCORDANCE WITH TABLE 4.2.1. PER TABLE 4.2.1: |
| 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL |
| BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| |
| 2. PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| |
| 3. PER SECTION 18.3.4.1 (NFPA 1), FIRE HYDRANTS SHALL |
| BE PROVIDED WITH CLEARANCES OF 7?-6? TO THE FRONT AND |
| SIDES AND 4? TO THE BACKSIDE. |
| |
| 4. PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT |
| ACCESS ROADS SHALL HAVE A SURFACE DESIGNED TO |
| ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 32 TONS. |
| ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT |
| LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL |
| CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES. |
| |
| STAIRS FOR TRAILERS |
| |
| 5. GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED |
| AT THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, |
| MEZZANINE, ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. |
| OPEN GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH |
| DIAMETER SPHERE UP TO A HEIGHT OF 34-INCHES. THE |
| TRIANGULAR OPENINGS FORMED BY THE RISER, TREAD AND |
| BOTTOM ELEMENT OF THE GUARDRAIL SHALL PROHIBIT THE |
| PASSAGE OF A 6-INCH DIAMETER SPHERE. |
| |
| HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR. |
| HANDRAILS SHALL BE LOCATED NOT LESS THAN 34 INCHES AND |
| NOT MORE THAN 38 INCHES ABOVE THE SURFACE OF THE TREAD, |
| MEASURED VERTICALLY TO THE TOP OF THE RAIL FROM THE |
| LEADING EDGE OF THE TREAD. HANDRAIL ENDS SHALL BE |
| RETURNED TO THE WALL OR FLOOR OR SHALL TERMINATE AT |
| NEWEL POSTS. HANDRAIL CROSS SECTION SHALL HAVE A |
| DIAMETER OF NOT LESS THAN 1.25 INCHES AND NOT MORE THAN |
| 2 INCHES. |
| |
| STAIR RISERS SHALL BE BETWEEN 4 INCHES AND 7 INCHES IN |
| HEIGHT. STAIRS SHALL BE SLIP RESISTANT AND HAVE A |
| MINIMUM TREAD DEPTH OF 11 INCHES AND PREVENT THE |
| ACCUMULATION OF WATER. |
| |
| STAIRS SHALL HAVE LANDINGS AT DOOR OPENINGS. |
| |
| STAIRS AND EGRESS COMPONENTS SHALL CONFORM TO THE LIFE |
| SAFETY REQUIREMENTS OF CHAPTER 7 OF NFPA 101 FLORIDA |
| 2012 EDITION. |
| |
| 6. PROVIDE ILLUMINATED EXIT SIGNS FOR ALL EXIT DOORS. |
| |
| 7. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM IS |
| REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP DRAWINGS, |
| ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY |
| THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION. |
| GJT |
| |