Plan Review Notes For Permit 15080661 |
Permit Number |
15080661 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-10-05 14:55:14 | THIS SET OF DRAWINGS WAS SO SLOPPY THAT I ACCIDENTLY | | STAMPED THE PLANS AS PASSED. PLEASE NOTE THAT .I | | COMPARED THE PANEL SCHEDULES SUBMITTED I NOTICED A | | MISMATCH. CORRECT THE SUBMITTAL SO THAT THE LOAD CALCS | | AND THE PANEL SCHEDULES MATCH ON BOTH SET OF DRAWINGS. | | FURTHERMORE, PROVIDE A SITE PLAN INDICATING THE | | LOCATION OF THE SOURCE OF POWER AND MAIN DISCONNECT. | | WHEN YOU RESUBMIT, PLEASE STAPLE ALL THE SHEETS OF EACH | | SET AND ATTACH THEM TO THE MANUFACTURERS DRAWINGS FOR | | COMPARISON. |
|