2015-10-05 14:55:14THIS SET OF DRAWINGS WAS SO SLOPPY THAT I ACCIDENTLY
 STAMPED THE PLANS AS PASSED. PLEASE NOTE THAT .I
 COMPARED THE PANEL SCHEDULES SUBMITTED I NOTICED A
 MISMATCH. CORRECT THE SUBMITTAL SO THAT THE LOAD CALCS
 AND THE PANEL SCHEDULES MATCH ON BOTH SET OF DRAWINGS.
 FURTHERMORE, PROVIDE A SITE PLAN INDICATING THE
 LOCATION OF THE SOURCE OF POWER AND MAIN DISCONNECT.
 WHEN YOU RESUBMIT, PLEASE STAPLE ALL THE SHEETS OF EACH
 SET AND ATTACH THEM TO THE MANUFACTURERS DRAWINGS FOR
 COMPARISON.