Plan Review Notes
Plan Review Notes For Permit 15080661
Permit Number 15080661
Review Stop B
Sequence Number 1
Notes
Date Text
2015-09-12 14:26:35****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. BASED ON THE SITE PLAN PROVIDED, IT APPEARS THAT THE
 PROPOSED LOCATION FOR THIS SALES TRAILER IS 4847 FRED
 GLADSTONE DRIVE. SUBMIT A CHANGE OF ADDRESS THROUGH THE
 FRONT COUNTER OR REVISE THE SITE PLAN TO SHOW THE
 PROPOSED SALES TRAILER RELATIVE TO THE LOT LINES, FBC
 107.
  
 2. SCOPE NOT CLEAR, FBC 107.
  
 COMPLETE PLANS WERE SUBMITTED FOR A "MODULAR
 STRUCTURE." PLEASE SEE FS 553.80, MODULAR STRUCTURES
 REQUIRE PLAN REVIEW AND APPROVAL BY THE STATE. IF THE
 MODULAR INSTALLATION IS PROPOSED, PROVIDE THE STATE
 APPROVED PLANS AND STATE APPROVAL COVER SHEET WHICH
 SHOWS THE APPROVAL NUMBER. THIS SHOULD BE ON THE
 INSIGNIA.
  
 SOMEONE ADDED PAGES AT SOME POINT IN THE REVIEW
 PROCESS. IF THESE PAGES WERE SUBMITTED AFTER OTHER
 REVIEWS WERE COMPLETE, RE-REVIEW BY THOSE TRADES IS
 REQUIRED. NO RESUBMITTAL FORM WAS PROVIDED.
  
 IF THE PLANS PREPARED BY REBECCA M. GATES ARE PROPOSED
 RATHER THAN THE PLAN WHICH APPEARS TO BE A DCA APPROVED
 MODULAR, PLEASE NOTE THE FOLLOWING PER STATE OF
 FLORIDA:
  
 CAN AN EXISTING MODULAR BUILDING BE MODIFIED OR
 RENOVATED?
  
 YES. ONSITE MODIFICATIONS TO EXISTING MODULAR BUILDINGS
 MUST BE PERMITTED AND INSPECTED BY THE JURISDICTION
 HAVING AUTHORITY (LOCAL BUILDING DEPARTMENT). ORIGINAL
 PLANS (OR ?AS-BUILT? PLANS) AND ANY MODIFICATIONS MUST
 BE PROVIDED TO THE LOCAL BUILDING DEPARTMENT. WHEN
 INSPECTED BY THE LOCAL BUILDING DEPARTMENT, THE
 DCA/DBPR INSIGNIA SHALL BE REMOVED AND RETURNED TO
 DBPR, AND A CERTIFICATE OF OCCUPANCY BE ISSUED IN LIEU
 OF THE DCA/DBPR INSIGNIA. RECERTIFICATION BY THE LOCAL
 JURISDICTION IS ONLY APPLICABLE FOR THAT JURISDICTION
 (NOT STATEWIDE).
  
 PLANS PREPARED BY REBECCA M. GATES SHOULD INCLUDE
 GOVERNING CODE. THE MODULAR PLANS ARE REQUIRED TO BE
 UPDATED TO CURRENT CODE.
  
 IN ADDITION TO THE CHANGE IN FLOOR PLAN, IT APPEARS
 THAT A DOOR HAS BEEN ELIMINATED AND A WINDOW IS
 PROPOSED, BUT NO DETAIL WAS PROVIDED. PROVIDE A
 STRUCTURAL DETAIL AND INCLUDE WIND DESIGN CRITERIA FBC
 1603.1.4. A PRODUCT APPROVAL REVIEWED BY DESIGNER OF
 RECORD REQUIRED.
  
 A COMPLETE CHECKLIST CANNOT BE PROVIDED AS INTENT IS
 NOT ENTIRELY CLEAR.
  
 3. PER ATCOUNCIL.ORG, THIS LOCATION IS RISK CATEGORY II
 167 MPH. PLANS SUBMITTED ARE LIMITED TO 165 MPH, SEE
 SHEET C1, FBC 1609. PER THE STATE OF FLORIDA, IF AN
 EXISTING MANUFACTURED (MODULAR) BUILDING IS MOVVED TO A
 NEW LOCATION, THE RELOCATED BUILDING SHALL COMPLY WITH
 THE WIND SPEED OF THE NEW LOCATION.
  
 4. SHOW 18 IN MANEUVERING CLEARANCE FOR DOORS, PULL
 SIDE, FBC ACCESSIBILITY 404.2.4.1, ROOMS 4 AND 5.
  
 5. FOR THE NEW FLOOR PLAN, PROVIDE DETAILS WHICH SHOW
 COMPLIANCE WITH ALL REQUIREMENTS OF FBC 5TH EDITION
 ACCESSILIBITY.
  
 5. STAIR, RAMP, LANDING, RAILING DETAILS NOT PROVIDED,
 FBC CHAPTER 10, FBC ACCESSIBILITY.
  
 6. SHEET SP1 SHOWS 38.8 FT FROM PROPOSED SALES OFFICE
 TO EXISTING RESNICK BUILDING. REVISE TO SHOW ASSUMED
 PROPERTY LINE BETWEEN THE TWO BUILDINGS, FBC 705.3 AND
 SHOW COMPLIANCE WITH FBC TABLES 602, 705.8.
  
 7. FOR IMPACT FEE PURPOSES, PROVIDE THE REMOVAL
 AGREEMENT WHEREIN OWNER AGREES THAT THE PROPOSED
 TEMPORARY SALES TRAILER WILL BE REMOVED BY A CERTAIN
 DATE (PER WILLIE SWOPE). IF THIS DOCUMENT CANNOT BE
 PROVIDED, AN IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY
 IS REQUIRED. 561-233-5025 FOR MORE INFORMATION.
  
 8. IMPACT PROTECTION REQUIRED, SEE SITE INSTALLED
 ITEMS, FBC 1609.1.4. IF SHUTTERS ARE PROPOSED, PROVIDE
 THE PRODUCT APPROVAL AND COMPLETE THE SAMPLE
 INSTALLATION SCHEDULE:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/SCHEDULE_FOR_INSTALLATION.PDF
  
  