2015-09-12 14:26:35 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. BASED ON THE SITE PLAN PROVIDED, IT APPEARS THAT THE |
| PROPOSED LOCATION FOR THIS SALES TRAILER IS 4847 FRED |
| GLADSTONE DRIVE. SUBMIT A CHANGE OF ADDRESS THROUGH THE |
| FRONT COUNTER OR REVISE THE SITE PLAN TO SHOW THE |
| PROPOSED SALES TRAILER RELATIVE TO THE LOT LINES, FBC |
| 107. |
| |
| 2. SCOPE NOT CLEAR, FBC 107. |
| |
| COMPLETE PLANS WERE SUBMITTED FOR A "MODULAR |
| STRUCTURE." PLEASE SEE FS 553.80, MODULAR STRUCTURES |
| REQUIRE PLAN REVIEW AND APPROVAL BY THE STATE. IF THE |
| MODULAR INSTALLATION IS PROPOSED, PROVIDE THE STATE |
| APPROVED PLANS AND STATE APPROVAL COVER SHEET WHICH |
| SHOWS THE APPROVAL NUMBER. THIS SHOULD BE ON THE |
| INSIGNIA. |
| |
| SOMEONE ADDED PAGES AT SOME POINT IN THE REVIEW |
| PROCESS. IF THESE PAGES WERE SUBMITTED AFTER OTHER |
| REVIEWS WERE COMPLETE, RE-REVIEW BY THOSE TRADES IS |
| REQUIRED. NO RESUBMITTAL FORM WAS PROVIDED. |
| |
| IF THE PLANS PREPARED BY REBECCA M. GATES ARE PROPOSED |
| RATHER THAN THE PLAN WHICH APPEARS TO BE A DCA APPROVED |
| MODULAR, PLEASE NOTE THE FOLLOWING PER STATE OF |
| FLORIDA: |
| |
| CAN AN EXISTING MODULAR BUILDING BE MODIFIED OR |
| RENOVATED? |
| |
| YES. ONSITE MODIFICATIONS TO EXISTING MODULAR BUILDINGS |
| MUST BE PERMITTED AND INSPECTED BY THE JURISDICTION |
| HAVING AUTHORITY (LOCAL BUILDING DEPARTMENT). ORIGINAL |
| PLANS (OR ?AS-BUILT? PLANS) AND ANY MODIFICATIONS MUST |
| BE PROVIDED TO THE LOCAL BUILDING DEPARTMENT. WHEN |
| INSPECTED BY THE LOCAL BUILDING DEPARTMENT, THE |
| DCA/DBPR INSIGNIA SHALL BE REMOVED AND RETURNED TO |
| DBPR, AND A CERTIFICATE OF OCCUPANCY BE ISSUED IN LIEU |
| OF THE DCA/DBPR INSIGNIA. RECERTIFICATION BY THE LOCAL |
| JURISDICTION IS ONLY APPLICABLE FOR THAT JURISDICTION |
| (NOT STATEWIDE). |
| |
| PLANS PREPARED BY REBECCA M. GATES SHOULD INCLUDE |
| GOVERNING CODE. THE MODULAR PLANS ARE REQUIRED TO BE |
| UPDATED TO CURRENT CODE. |
| |
| IN ADDITION TO THE CHANGE IN FLOOR PLAN, IT APPEARS |
| THAT A DOOR HAS BEEN ELIMINATED AND A WINDOW IS |
| PROPOSED, BUT NO DETAIL WAS PROVIDED. PROVIDE A |
| STRUCTURAL DETAIL AND INCLUDE WIND DESIGN CRITERIA FBC |
| 1603.1.4. A PRODUCT APPROVAL REVIEWED BY DESIGNER OF |
| RECORD REQUIRED. |
| |
| A COMPLETE CHECKLIST CANNOT BE PROVIDED AS INTENT IS |
| NOT ENTIRELY CLEAR. |
| |
| 3. PER ATCOUNCIL.ORG, THIS LOCATION IS RISK CATEGORY II |
| 167 MPH. PLANS SUBMITTED ARE LIMITED TO 165 MPH, SEE |
| SHEET C1, FBC 1609. PER THE STATE OF FLORIDA, IF AN |
| EXISTING MANUFACTURED (MODULAR) BUILDING IS MOVVED TO A |
| NEW LOCATION, THE RELOCATED BUILDING SHALL COMPLY WITH |
| THE WIND SPEED OF THE NEW LOCATION. |
| |
| 4. SHOW 18 IN MANEUVERING CLEARANCE FOR DOORS, PULL |
| SIDE, FBC ACCESSIBILITY 404.2.4.1, ROOMS 4 AND 5. |
| |
| 5. FOR THE NEW FLOOR PLAN, PROVIDE DETAILS WHICH SHOW |
| COMPLIANCE WITH ALL REQUIREMENTS OF FBC 5TH EDITION |
| ACCESSILIBITY. |
| |
| 5. STAIR, RAMP, LANDING, RAILING DETAILS NOT PROVIDED, |
| FBC CHAPTER 10, FBC ACCESSIBILITY. |
| |
| 6. SHEET SP1 SHOWS 38.8 FT FROM PROPOSED SALES OFFICE |
| TO EXISTING RESNICK BUILDING. REVISE TO SHOW ASSUMED |
| PROPERTY LINE BETWEEN THE TWO BUILDINGS, FBC 705.3 AND |
| SHOW COMPLIANCE WITH FBC TABLES 602, 705.8. |
| |
| 7. FOR IMPACT FEE PURPOSES, PROVIDE THE REMOVAL |
| AGREEMENT WHEREIN OWNER AGREES THAT THE PROPOSED |
| TEMPORARY SALES TRAILER WILL BE REMOVED BY A CERTAIN |
| DATE (PER WILLIE SWOPE). IF THIS DOCUMENT CANNOT BE |
| PROVIDED, AN IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY |
| IS REQUIRED. 561-233-5025 FOR MORE INFORMATION. |
| |
| 8. IMPACT PROTECTION REQUIRED, SEE SITE INSTALLED |
| ITEMS, FBC 1609.1.4. IF SHUTTERS ARE PROPOSED, PROVIDE |
| THE PRODUCT APPROVAL AND COMPLETE THE SAMPLE |
| INSTALLATION SCHEDULE: |
| |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/SCHEDULE_FOR_INSTALLATION.PDF |
| |
| |