2015-10-19 10:16:53 | 2ND REVIEW: FBC 2014 MECHANICAL | | PERMIT #15080653 | | 10/19/15 | | | | 1) THE 5600 SF CONDITIONED AREA LISTED ON ENERGY FORM | | 506-2014 DOES NOT APPEAR TO MATCH THE SQUARE FOOT AREA | | SHOWN ON SHEET M6.1 AS MEASURED BY SCALE. PLEASE | | PROVIDE COMPLETE FLOOR PLAN DIMENSIONS ON THE PLAN. | | 2) THE WIND LOAD DESIGN CRITERIA ON SHEET A3.1 | | INDICATES -72.5 PSF DESIGN PRESSURE AT THE ROOF. PLEASE | | CLARIFY WHICH RTU THIS PRESSURE IS APPLICABLE TO- THE | | RELOCATED RTU # 1-1 OR THE NEW RTU-3. | | 3) THE SUBMITTED N0A #15-0218.11 (STEEL CURB FOR | | CARRIER RTU'S) INDICATES ON SHEET 1 OF 5 THAT IT IS | | "ACCEPTABLE FOR ALL CARRIER UNITS WITH THE FOLLOWING | | MODEL NUMBERS- 48/50XXYY". IT APPEARS THAT THE NOA MAY | | BE APPLICABLE FOR THE NEW RTU-3 (50TC*D12-6), HOWEVER | | EVIDENCE MUST BE PROVIDED TO VERIFY THE CURB CAN BE | | USED FOR THE RELOCATED RTU #1-1. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|