Text |
2015-09-01 07:23:55 | |
| BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15080653 |
| ADD: 1819 OKEECHOBEE RD. |
| CONT: GLOBAL CONSTRUCTION ASSOCIATES |
| TEL: (954)971-1810 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. SEPT. 01/2015 |
| ACTION: DENIED |
| |
| 1) COVERSHEET ?T: |
| |
| 1A) INDICATES THE PLANS WERE DESIGNED TO THE 2010 FBC, |
| PLEASE NOTE THE 2014, 5TH EDITION WAS ADOPTED STATEWIDE |
| JUNE 30/ 2015. PLEASE UPDATE PLANS. |
| |
| 1B) THE CONSTRUCTION TYPE IS LISTED AS A BLDG TYPE IV |
| THE ORIGINAL BUILDING WAS BUILT UNDER THE 2001 FBC-B. |
| THAT CODE AND BUILDING TYPE IS THE EQUAL TO UNDER THE |
| 2014 FBC-B IIB. PLEASE UPDATE PLANS. |
| |
| 2) SHEET A1.1: |
| |
| 2A) THE TRAINING ROOM IS APPROXIMATELY 1430 SQ. FT./ 20 |
| SQ. FT. NET= 72 OCCUPANT LOAD. SEE THE 2014 FBC-B TABLE |
| 1014.1.2. |
| |
| 2B) PLEASE PROVIDE A LIFE SAFETY PLAN FOR THIS TENANT, |
| IN THE TRAINING ROOM WITH A OCCUPANT LOAD OF 72 |
| REQUIRES (2) MEANS OF EGRESS. |
| 2014 FBC-B TABLE 1015.1 BUSINESS OCCUPANCY MAXIMUM |
| OCCUPANTS WITH ONE EXIT IS 49. |
| 2014 FBC-B TABLE 1016.2 EXIT ACCESS TRAVEL |
| |
| 2C) THE EXISTING (1) HOUR FIRE RATED WALL BETWEEN WARE |
| HOUSES 103 & 104 INDICATES IN THE WALL LEGEND A (1) |
| HOUR FIRE RATED WALL TO REMAIN. IN THIS WALL THERE IS A |
| DOOR IDENTIFIED AS ER1, THE DOOR SCHEDULE FOUND ON |
| SHEET A3.1 INDICATES IN THE DOOR NOTES THIS DOOR IS TO |
| BE RELOCATED. WHAT IS GOING TO HAPPEN IN THIS OPENING |
| IN THE RATED WALL, IS IT TO BE CLOSED UP? 2014 FBC-B |
| 716.5/ TABLE 716.5 FIRE DOOR AND SHUTTER ASSEMBLIES. |
| |
| 2D) THE EXISTING (1) HOUR FIRE RATED WALL BETWEEN WARE |
| HOUSE 102 & 104 THE PLANS INDICATE A NEW 12?-0? WIDE |
| OPENING IN NOTE # 5 FOUND ON THIS PLAN. THERE IS NO |
| INFORMATION ON THIS OPENING IN THE DOOR SCHEDULE ON |
| SHEET A3.1. NOTE SHEET A1.1 WALL LEGEND INDICATES THIS |
| WALL TO BE A (1) HOUR FIRE RATED WALL. |
| |
| 3) SHEET A3.2 DETAIL # A6 INDICATES IN ROOF TOP A/C |
| CURB INSTALLATIONS? WITH NEW STEEL FRAMING MEMBERS |
| BEING WELDED INTO PLACE. PLEASE NOTE THE FRAMING AND |
| WELDED CONNECTIONS WILL REQUIRE A 3RD PARTY TO CERTIFY |
| WORK COMPLETED IN THIS AREA OR A RESIDENT INSPECTOR |
| ONSITE WITH PAPERWORK FILED WITH CITY BEFORE PERMIT |
| ISSUANCE, PLEASE INDICATE IN WRITING YOUR CHOICE. |
| RESIDENT INSPECTOR FORMS MUST BE FILED OUT AND RETURNED |
| FOR REVIEW. |
| 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 110.3.9. |
| SUCH INSPECTORS SHALL BE ADEQUATELY PRESENT AT TIMES |
| WORK IS UNDERWAY ON THE STRUCTURAL ELEMENTS OF THE |
| BUILDING. SUCH INSPECTORS SHALL BE A REGISTERED |
| ARCHITECT, OR ENGINEER, OR A PERSON LICENSED UNDER |
| CHAPTER 468, PART XII, FLORIDA STATUTES. SUCH |
| INSPECTORS SHALL SUBMIT WEEKLY PROGRESS REPORTS |
| INCLUDING THE DAILY INSPECTIONS TO THE BUILDING |
| OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF |
| THE RESIDENT INSPECTOR. |
| |
| 3A) 110.4 INSPECTION AGENCIES. THE BUILDING OFFICIAL IS |
| AUTHORIZED TO ACCEPT REPORTS OF APPROVED INSPECTION |
| AGENCIES, PROVIDED SUCH AGENCIES SATISFY THE |
| REQUIREMENTS AS TO QUALIFICATIONS AND RELIABILITY. |
| |
| 3B) 110.5 INSPECTION REQUESTS. IT SHALL BE THE DUTY OF |
| THE HOLDER OF THE BUILDING PERMIT OR THEIR DULY |
| AUTHORIZED AGENT TO NOTIFY THE BUILDING OFFICIAL WHEN |
| WORK IS READY FOR INSPECTION. IT SHALL BE THE DUTY OF |
| THE PERMIT HOLDER TO PROVIDE ACCESS TO AND MEANS FOR |
| INSPECTIONS OF SUCH WORK THAT ARE REQUIRED |
| BY THIS CODE. |
| |
| 3C) 110.6 APPROVAL REQUIRED. WORK SHALL NOT BE DONE |
| BEYOND THE POINT INDICATED IN EACH SUCCESSIVE |
| INSPECTION WITHOUT FIRST OBTAINING THE APPROVAL OF THE |
| BUILDING INSPECTOR. THE BUILDING OFFICIAL, UPON |
| NOTIFICATION, SHALL MAKE THE REQUESTED INSPECTIONS AND |
| SHALL EITHER INDICATE THE PORTION OF THE CONSTRUCTION |
| THAT IS SATISFACTORY AS COMPLETED, OR NOTIFY THE PERMIT |
| HOLDER OR HIS OR HER AGENT WHEREIN THE SAME FAILS TO |
| COMPLY WITH THIS CODE. ANY PORTIONS THAT DO NOT COMPLY |
| SHALL BE CORRECTED AND SUCH PORTION SHALL NOT BE |
| COVERED OR CONCEALED UNTIL AUTHORIZED BY THE BUILDING |
| OFFICIAL. |
| |
| 4) SHEET A3.2 DETAIL # A6 & M6.1 BOTH SHOW NEW OR |
| REPOSITIONED ROOF TOP CURBS BEING INSTALLED ON THE |
| ROOF. PLEASE SUBMIT PRODUCT APPROVALS FOR THE NEW |
| CURBS. 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING |
| |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(D) ROOFING PRODUCTS AND ASSEMBLIES/ ROOF TOP CURBS |
| |
| 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS. |
| |
| 6) THE PLANS DO NOT PROVIDE THE WIND DESIGN CRITERIA |
| FOR THE ROOF TOP CURBS. 2014 FBC-B 1603.1.4 WIND DESIGN |
| DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 6.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| |
| 6.2. RISK CATEGORY. |
| |
| 6.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. |
| |
| 6.. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 6.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| M2). |
| |
| 7) THE PLANS WILL NEED TO SUPPLY THE CONNECTION OF THE |
| RTU UNITS AND EXHAUST FANS TO THE ROOF TOP CURBING, TO |
| RESIST THE EFFECTS OF UPLIFT, SLIDING AND OR |
| OVERTURNING MOMENT. 2014 FBC-B 1609.6.4.4.1 COMPONENTS |
| & CLADDING |
| |
| 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |