2015-08-26 17:09:501ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080587
 8/26/15
  
 1) SHEETS M000 & M200: CORRECT THE O/A CALCULATIONS TO
 INDICATE 475 CFM'S IN COMPLIANCE WITH TABLE 403.3
 FBC-14 MECHANICAL. THE TABLE INDICATES AN OCCUPANT
 DENSITY OF 70 PERSONS PER 1000 SQ. FT. (.07 X 360 SQ.
 FT.= 26 PERSONS) X 10 CFM EACH = 260 CFM + 215 CFM =
 475 CFM. PLEASE REVISE THE TABLE AND THE RTU SCHEDULE,
 AND PLACE DIMENSIONS ON THE FLOOR PLANS SO SQUARE
 FOOTAGE CALCULATIONS CAN BE VERIFIED.
  