Plan Review Notes For Permit 15080587 |
Permit Number |
15080587 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-08-26 17:09:50 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #15080587 | | 8/26/15 | | | | 1) SHEETS M000 & M200: CORRECT THE O/A CALCULATIONS TO | | INDICATE 475 CFM'S IN COMPLIANCE WITH TABLE 403.3 | | FBC-14 MECHANICAL. THE TABLE INDICATES AN OCCUPANT | | DENSITY OF 70 PERSONS PER 1000 SQ. FT. (.07 X 360 SQ. | | FT.= 26 PERSONS) X 10 CFM EACH = 260 CFM + 215 CFM = | | 475 CFM. PLEASE REVISE THE TABLE AND THE RTU SCHEDULE, | | AND PLACE DIMENSIONS ON THE FLOOR PLANS SO SQUARE | | FOOTAGE CALCULATIONS CAN BE VERIFIED. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|