Plan Review Notes
Plan Review Notes For Permit 15080504
Permit Number 15080504
Review Stop M
Sequence Number 3
Notes
Date Text
2015-10-19 09:07:283RD REVIEW: FBC 2014 5TH ED.
  
 A PLAN AND PARTIALLY COMPLETED ENERGY FORM HAS BEEN
 SUPPLIED. THE IS NOT ACCEPTABLE AS THE DUCT MATERIAL
 AND DIMENSIONS OF VARIOUS PORTIONS OF THE DUCT SYSTEM
 ARE NOT IDENTIFIED. THE ENERGY SUBMITTAL IS NOT FILLED
 OUT, THERE IS NO EQUIPMENT SIZING CALCULATION PROVIDED.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN
  
 FBC-ER403.6.1 PROVIDE A SIZING CALCULATION.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  