2015-10-19 09:07:28 | 3RD REVIEW: FBC 2014 5TH ED. |
| |
| A PLAN AND PARTIALLY COMPLETED ENERGY FORM HAS BEEN |
| SUPPLIED. THE IS NOT ACCEPTABLE AS THE DUCT MATERIAL |
| AND DIMENSIONS OF VARIOUS PORTIONS OF THE DUCT SYSTEM |
| ARE NOT IDENTIFIED. THE ENERGY SUBMITTAL IS NOT FILLED |
| OUT, THERE IS NO EQUIPMENT SIZING CALCULATION PROVIDED. |
| |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC, |
| AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR THE DESIGN |
| |
| FBC-ER403.6.1 PROVIDE A SIZING CALCULATION. |
| |
| STEVEN KENNEDY, CBO |