Plan Review Notes
Plan Review Notes For Permit 15080504
Permit Number 15080504
Review Stop M
Sequence Number 2
Notes
Date Text
2015-10-05 15:21:112ND REVIEW: FBC 2014 5TH ED.
  
 THERE WAS NO MECHANICAL OR IN THE ORIGINAL NOR THE
 RE-SUBMITTAL. THE COMMENTS BELOW ARE REPEAT COMMENTS.
  
 THERE IS A LACK OF DETAIL AND INFORMATION TO DETERRMINE
 COMPLIANCE WITH THE MECHANICAL CODE.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 WHAT ARE YOU DOING IN TERMS OF RELOCATING THE AHU? IF
 PLACING IN THE ATTIC, PROVIDE DETAIL TO DEMONSTRATE
 COMPLIANCE WITH THE FOLLOWING:
  
 FBC-R M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES
 (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE
 APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS
 OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY
 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE.
  
 FBC-R M1305.1.3.1 ELECTRICAL REQUIREMENTS.
 A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34.
  
 FBC-R M1305.1.3.2 AIR-HANDLING UNITS.
 AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE
 FOLLOWING CONDITIONS ARE MET:
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
  
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  