Plan Review Notes
Plan Review Notes For Permit 15080504
Permit Number 15080504
Review Stop E
Sequence Number 1
Notes
Date Text
2015-08-14 10:14:331ST REVIEW: FBC 2014 5TH ED./ NEC2011
  
 NO ELECTRICAL DETAILS ARE PROVIDED; ELECTRICAL
 MODIFICATIONS ARE REQUIRED IN THE NEWLY ARRANGED
 KITCHEN, BEDROOMS, AND THE BATHROOM AND TO FOR THE A/C
 CONDENSER RELOCATION AND FOR ASSURANCE OF SMOKE AND CO
 DETECTORS. PROVIIDE AN ELECTRICAL PLAN PER THE MINIMUM
 CRITERIA OF FBC 107 AND DEMONSTRATE COMPLIANCE WITH THE
 FOLLOWING:
  
 FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO
 FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS.
 FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10
 FEET OF EACH SLEEPING ROOM.
 NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES
 SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE
 BRANCH CIRCUITS.
 NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN
 25? OF MECHANICAL EQUIPMENT.
 NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME
 POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET WHERE
 WALLS ARE BEING MODIFIED.
 NEC 210.12B - OUTLETS TO BE AFCI PROTECTED.
 NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER