Plan Review Notes For Permit 15080504 |
Permit Number |
15080504 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-08-14 10:14:33 | 1ST REVIEW: FBC 2014 5TH ED./ NEC2011 | | | | NO ELECTRICAL DETAILS ARE PROVIDED; ELECTRICAL | | MODIFICATIONS ARE REQUIRED IN THE NEWLY ARRANGED | | KITCHEN, BEDROOMS, AND THE BATHROOM AND TO FOR THE A/C | | CONDENSER RELOCATION AND FOR ASSURANCE OF SMOKE AND CO | | DETECTORS. PROVIIDE AN ELECTRICAL PLAN PER THE MINIMUM | | CRITERIA OF FBC 107 AND DEMONSTRATE COMPLIANCE WITH THE | | FOLLOWING: | | | | FBC- 107.3.5.3 ? PROVIDE SMOKE DETECTORS PURSUANT TO | | FBC-R 314.3.1 AS REQUIRED FOR NEW DWELLINGS. | | FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 | | FEET OF EACH SLEEPING ROOM. | | NEC 210.52 (B) (3) - KITCHEN COUNTER TOP RECEPTACLES | | SHALL BE SUPPLIED BY NO FEWER THAN TWO SMALL APPLIANCE | | BRANCH CIRCUITS. | | NEC 210.63 - PROVIDE A GFI SERVICE OUTLET FOR WITHIN | | 25? OF MECHANICAL EQUIPMENT. | | NEC 210.52(A)(1)&(2) OUTLET SPACING, IT APPEARS SOME | | POINTS ALONG THE WALL EXCEED 6? FROM AN OUTLET WHERE | | WALLS ARE BEING MODIFIED. | | NEC 210.12B - OUTLETS TO BE AFCI PROTECTED. | | NEC 406.11- PROVIDE TAMPER RESISTANT RECEPTACLES. | | | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|