Plan Review Notes For Permit 15080469 |
Permit Number |
15080469 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-09-01 16:53:47 | ****CORRECTIONS**** | | | | ART LANGE - BUILDING INSPECTOR | | 561-805-6667 [email protected] | | FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA | | RESIDENTIAL CODE 2015 5TH EDITION | | | | 9/1/15 | | | | | | 1. FBC 3105.4 AND FBC 3105.1 LOADS. PROVIDE DESIGN | | CRITERIA. THE WIND DESIGN LOADS FOR ANY FABRIC OR | | MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK | | REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND | | VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING | | CRITERIA: | | | | 1. MINIMUM WIND SPEED 105 MPH. | | | | 2. EXPOSURE CATEGORY B, C OR D AS DEFINED IN CHAPTER | | 16. PROVIDE WIND DESIGN CRITERIA. | | | | 2. PROVIDE AWNING HEIGHT FROM GRADE. FBC 3105.3.1.1 | | | | | | |
|