Date |
Text |
2015-08-25 15:48:34 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15080427 |
| ADD: 1645 PALM BEACH LAKES SUITES, 210,220, 230 & 240 |
| CONT: CHANDLER |
| TEL: (561)791-6934 |
| E-MAIL: JOHN@BUILDCCC. COM |
| |
| 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, |
| |
| 2014EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: TUES. AUGUST 25/2015 |
| ACTION: DENIED |
| |
| 1) SHEET A2 SHOWS AN EXISTING ATRIUM BUT THE SHARED |
| ATRIUM WALL BETWEEN THE TENANCY 210 & 240 DOES NOT |
| INDICATE ANY WALL RATING. 2014 FBC-B 404.6 ATRIUM |
| SPACES SHALL BE SEPARATED FROM ADJACENT SPACES BY A |
| 1-HOUR FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH |
| SECTION 707. |
| |
| 2) DISCREPANCY IN PLANS. FOR THE TENANT SPEARATION WALL |
| SHEET A2 INDICATES A DETAIL # 1/ A2 THERE IS NO SUCH |
| DETAIL, TYPO IT APPEARS THAT THE DETAIL IS FOUND ON |
| SHEET A3. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 3) DISCREPANCY IN PLANS SHEET A2 VERSES A5 THE DOOR |
| LEADING TO THE STAIRWELL CLOSEST TO UNIT # 240. THE 90 |
| MINUTE STAIRWELL DOOR SHOULD BE A INSWING DOOR INTHE |
| DIRECTION OF EXIT TRAVEL WITH OCCUPANT LOADS OF 50 OR |
| MORE PERSONS. 2014 FBC-B 1008.1.2 |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |