Notes |
Date |
Text |
2015-08-12 16:47:55 | 1ST REVIEW: FBC 2014 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | 561-805-6711 | | [email protected] | | | | | | COMMENTS: | | 1. CSST PIPING TO WATER HEATER SIZED WRONG SHALL BE | | 1IN. TABLE 402.4[15] | | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | FBC-2014 FUEL GAS CODE SEC. 304. | | 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE | | SEC. 502 THRU 505. | | 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | |
|