Plan Review Notes
Plan Review Notes For Permit 15080380
Permit Number 15080380
Review Stop P
Sequence Number 1
Notes
Date Text
2015-08-18 03:57:251) SUBMIT A FLOOR PLAN FOR THE ENTIRE UNIT SHOWING ALL
 THE BATHROOMS /.WPB AMEND. TO FBC SEC.107.3.5.1.
 2) SUBMIT FIRE SAFING DETAILS FOR ANY PIPING THAT
 PENETRATES A FIRE RATED PARTITION OF SMOKE
 PARTITION.COMPLY WITH 2014 FBC SEC. 714.
 3) SHT.A-1.0 - THE PLANS REFER TO THE 2010 FBC AND IN
 GENERAL NOTE #9, THE 2007/2009 CODES ARE REFERENCED.
 DELETE THESE REFERENCES AND INSERT THE 2014 FBC FAMILY
 OF CODES.
 4) THE PLANS LIST THE OCCUPANCY TYPE OF THIS STRUCTURE
 AS AN R-3 WHEN IT IS CLEARLY AN R-2 OCCUPANCY.CHANGE
 THE OCCUPANCY TYPE TO READ R-2.
 5) THE PLANS ARE VAGUE AS TO THE SCOPE OF PLUMBING WORK
 TO BE DONE. IS THE WATER HEATER BEING REPLACED?
 IDENTIFY IT ON THE PLANS.IDENTIFY ON THE PLANS WHAT
 EXACTLY IS BEING REPLACED AND WHAT IS EXISTING TO
 REMAIN.
 6) SHT A2.1.-DETAIL #4 - THERE IS A NOTE STATING "NEW
 WASTE LINE TO EXISTING WASTE STACK" BUT THERE IS NO
 PIPING SHOWN. CLARIFY.
 7) INDICATE ON THE PLANS IF ANY WORK IS TO BE DONE IN
 THE OTHER BATHROOM. WPB AMEND, TO FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  