Plan Review Notes
Plan Review Notes For Permit 15080380
Permit Number 15080380
Review Stop B
Sequence Number 1
Notes
Date Text
2015-08-14 11:28:33 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080380
 ADD: 801 S. OLIVE SUITE # 1409
 CONT: ANDERSON CONSTRUCTION GROUP, LLC
 TEL: (561)255-5464
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. AUGUST 14/ 2015
 ACTION: DENIED
  
 1) THE COVERSHEET A-1.0 :
 1A) LIST THE CODE DESIGN AS THE 2010 FBC- EXISTING
 BUILDING. PLEASE BE AWARE THAT THE 2014 FBC-EXISTING
 BUILDING WAS ADOPTED STATEWIDE ON JUNE 30, 2015. PLEASE
 UPDATE PLANS.
  
 1B) MINIMUM BLDG. TYPE IS LISTED AS A TYPE V. PLEASE
 NOTE THIS IS A HIGH-RISE BLDG. THE 2014 FBC-B TABLE 503
 REQUIRES THIS TO BE A BLDG. TYPE 1A.
  
 1C) THE COVERSHEET ALSO LIST THE OCCUPANCY TYPE AS A
 R3. PLEASE NOTE THIS IS A SINGLE FAMILY DWELLING.
 CONDOMINIUMS ARE CONSIDERED A R2 PLEASE SEE THE 2014
 FBC-B 310.4 RESIDENTIAL GROUP R-2.
  
 2) SHEET A2.1;
  
 2A) SHOWS A FIRE RATED WALL BEING FILLED IN, THERE IS
 NO INFORMATION AS TO WHAT FRAMING MEMBERS ARE TO BE
 USED FOR THE INSTALATION OR FOR THE TYPE OF MATERIAL
 FOR A 1 HOUR FIRE RATED ASSEMBLY. 2014 FBC-B 708.3
 FIRE-RESISTANCE RATING. FIRE PARTITIONS SHALL HAVE A
 FIRERESISTANCE RATING OF NOT LESS THAN 1 HOUR.
  
 2B) THE FIRE RATED WALL WILL HAVE PENETRATIONS THROUGH
 THE DRYWALL, THERE HAS BEEN NO DETAILS SHOWING CODE
 COMPLIANCE FOR 2014 FBC-B 708.7 PENETRATIONS.
 PENETRATIONS OF FIRE PARTITIONS SHALL COMPLY WITH
 SECTION 714.
 714.3 FIRE-RESISTANCE-RATED WALLS.
 PENETRATIONS INTO OR THROUGH FIRE WALLS, FIRE BARRIERS,
 SMOKE BARRIER WALLS AND FIRE PARTITIONS SHALL COMPLY
 WITH SECTIONS 714.3.1 THROUGH 714.3.3. PENETRATIONS IN
 SMOKE BARRIER WALLS SHALL ALSO COMPLY WITH SECTION
 714.5.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  