2015-09-28 19:03:29 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW | | COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | 1- EQUIPMENT SIZING CALCULATIONS NEED TO BE DONE TO THE | | ACTUAL BUILDING ORIENTATION AS REQUIRED BY SEC. R403.61 | | OF FBC-ENERGY CONSERVATION, 5TH EDITION (2014). | | ACCORDING TO CALCULATIONS SUBMITTED THE ENTRY DOOR IS | | FACING NORTH. THIS I S NOT CORRECT. REVISE CALCULATIONS | | AS REQUIRED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|