2015-09-25 11:25:32 | SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW COMMENTS. |
| CODE: FBC 5TH EDITION (2014). |
| |
| 1- ARCHITECT TO UPDATE ALL PLANS AND NOTES. THE CODE IN |
| EFFECT IS THE 2014 CODE NOT THE 2010. REVISE AS |
| REQUIRED. CHAPTER 553 F.S. |
| |
| 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| COUNTY (2300 N. JOG RD) FOR IMPACT FEES ASSESSMENT. |
| BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| THE UNIFIED LAND DEVELOPMENT CODE. |
| |
| 3- EXTERIOR WALL SECTION ON SHEET 2 OF 2: |
| A) SPECIFY VENTILATION AS REQUIRED BY SEC. R806 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). SPECIFY SIZE AND |
| SPACING OF VENTS. |
| NOTE: KEEP IN CONSIDERATION RIGID VENT PRODUCT APPROVAL |
| SUBMITTED. |
| |
| B) SPECIFY THE 6 INCHES HEIGHT ABOVE THE FINISHED GRADE |
| AS REQUIRED BY SEC. R404.1.6 OF FBC-RESIDENTIAL, 5TH |
| EDITION (2014). |
| NOTE: KEEP IN CONSIDERATION THE 3/4" RECESS AND THE |
| SIZE OF FOOTING SPECIFIED. ALSO REMEMBER THAT 12" IS |
| REQUIRED TO BE BELOW THE FINISH GRADE. |
| |
| C) PROVIDE ROOF SHEATHING NAILING SPECIFICATIONS. |
| SPECIFY NAIL TYPE (8D RING SHANK MIN.) AND SPACING AS |
| REQUIRED BY SEC. R803.2.3.1 OF FBC-RESIDENTIAL, 5TH |
| EDITION (2014). |
| |
| D) SPECIFY THE STUCCO THICKNESS AS REQUIRED BY TABLE |
| R702.1(1) OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| E) SPECIFY WALL SHEATHING NAIL TYPE AND SPACING. SEC. |
| R301 OF FBC-RESIDENTIAL, 5TH EDITION (2014) |
| |
| 4- DOOR #8 SHOWN ON FLOOR PLAN AND WEST ELEVATION DON'T |
| MATCH DOOR SPECIFIED ON THE DOOR SCHEDULE ON SHEET 1 OF |
| 2. SEE NUMBER OF PANELS AND REVISE AS REQUIRED TO |
| MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 5- SPECIFY THE DIMENSION FOR THE ROOF OVERHANG AND |
| PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE |
| FIRE RATING OVERHANG AS REQUIRED BY TABLE R302.1(1) OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 6- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| FOR ALL NEW WINDOWS AND DOORS OPENINGS. SPECIFY ALL |
| FRAMING MEMBERS AND FASTENERS. SEC. R301 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 7- PROVIDE THE DESIGN PRESSURES FOR ALL EXTERIOR DOORS. |
| ONLY THE WINDOWS DESIGN PRESSURES WERE GIVEN. SEC. R301 |
| OF FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| 8- ROOF FRAMING PLAN. SPECIFY ALL TRUSS CONNECTORS, |
| INCLUDING THE CONNECTORS TO TRUSSES RESTING ON EXISTING |
| ROOF SHEATHING. SEC. R301 OF FBC-RESIDENTIAL, 5TH |
| EDITION (2014). |
| |
| 9- ENERGY CALCULATIONS SUBMITTED TO HAVE THE |
| OWNER/AGENT CERTIFICATION AND DATE AT THE BOTTOM OF THE |
| FORM AS REQUIRED BY SEC. R103.1.1.2 OF FBC-ENERGY |
| CONSERVATION, 5TH EDITION (2014). |
| IMPORTANT: WINDOWS AND DOORS LABELS WITH U-FACTOR AND |
| SHGC FACTOR SPECIFIED ON THIS ENERGY CALCULATIONS WILL |
| BE REQUIRED. |
| |
| 10- THERE ARE TWO DIFFERENT PRODUCT APPROVALS SUBMITTED |
| FOR THE EXTERIOR SWING DOORS. FL15227.5 AND FL15446-R3. |
| PROVIDE ONLY ONE PRODUCT APPROVAL THAT MATCHES DOOR AS |
| SPECIFIED ON THE DOOR SCHEDULE. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| NOTE: CLEARLY MARK ON PRODUCT APPROVAL ENTRY DOOR, |
| MASTER BEDROOM DOOR, ETC. |
| |
| 11- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A) SLIDING GLASS DOOR #8 AS SHOWN ON PLANS AND DOOR |
| SCHEDULE. NOTE: SEE NUMBER OF PANELS. |
| |
| B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ROOF |
| FRAMING PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA |
| PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE |
| SPECIFIED CONNECTOR. OR DESIGN PROFESSIONAL TO LIST THE |
| FLORIDA PRODUCT APPROVAL NEXT TO THE SPECIFIED |
| CONNECTOR. |
| |
| 12- DESIGNER OF RECORD TO APPROVE IN WRITING ALL |
| PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| AMENDMENTS. |
| |
| 13- ARCHITECT TO CLARIFY BEDROOMS CASEMENT WINDOWS. |
| ARCHITECT'S EXTERIOR ELEVATIONS SHOW DOUBLE CASEMENT |
| WINDOWS ON EACH OPENING. DOUBLE CASEMENT WINDOWS DON'T |
| COMPLY WITH THE EGRESS REQUIREMENTS (SEC. R310) BECAUSE |
| A MULLION IS REQUIRED IN THE MIDDLE TO RESIST THE WIND |
| LOADS. |
| ON THE OTHER HAND CASEMENT WINDOWS NOA 14-0506.01 |
| SUBMITTED IS FOR SINGLE CASEMENT WINDOWS ONLY. REVISE |
| AS REQUIRED TO COMPLY WITH EGRESS AND PRODUCT APPROVAL |
| SUBMITTED. |
| |
| *** PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| |