Plan Review Notes
Plan Review Notes For Permit 15080378
Permit Number 15080378
Review Stop P
Sequence Number 1
Notes
Date Text
2015-08-19 13:48:551ST REVIEW: FBC 2014
  
 COMMENTS:
  
 1.PLEASE SHOW BREAKROOM SINK TO COMPLY WITH KNEE AND
 TOE SPACE . FBCA SEC 306.2 AND 306.3
 2. VANITY CAN NOT OVERLAP INTO TOILET CLEARANCE IN
 TOILET ROOM 1006 SHEET A-2.2 DETAIL C. FBCA SEC 604.3.1
 AND 604.3.2
 3. BACKFLOW PROTECTION SHALL BE PROVIDE FOR COFFEE
 MACHINE AND ICE MAKER. FBCPSEC. 608.16.10
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 561-805-6711
 [email protected]
  