Plan Review Notes
Plan Review Notes For Permit 15080378
Permit Number 15080378
Review Stop M
Sequence Number 1
Notes
Date Text
2015-08-14 14:39:321ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080378
 8/14/15
  
 1) REFERENCE SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION, AND PROVIDE HEAT LOAD CALCULATIONS FOR
 THE NEW MITSUBISHI MINI-SPLIT AC SYSTEM
 C403.2.1 CALCULATION OF HEATING AND COOLING LOADS.
 DESIGN LOADS SHALL BE DETERMINED IN ACCORDANCE WITH THE
 PROCEDURES DESCRIBED IN THE ASHRAE/ACCA STANDARD 183 OR
 ACCA MANUAL N AND SHALL BE ATTACHED TO THE CODE
 COMPLIANCE FORM SUBMITTED TO THE BUILDING DEPARTMENT
 WHEN THE BUILDING IS PERMITTED OR, IN THE EVENT THE
 MECHANICAL PERMIT IS OBTAINED AT A LATER TIME, THE
 SIZING CALCULATION SHALL BE SUBMITTED WITH THE
 APPLICATION FOR THE MECHANICAL PERMIT. HEATING AND
 COOLING LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD
 REDUCTIONS THAT ARE ACHIEVED WHEN ENERGY RECOVERY
 SYSTEMS ARE UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE
 WITH THE ASHRAE HVAC SYSTEMS AND EQUIPMENT HANDBOOK.
 ALTERNATIVELY, DESIGN LOADS SHALL BE DETERMINED BY AN
 APPROVED EQUIVALENT COMPUTATION PROCEDURE, USING THE
 DESIGN PARAMETERS SPECIFIED IN CHAPTER 3.
 2) SHEET M0.1: CORRECT THE HVAC DESIGN CONDITIONS IN
 ACCORDANCE WITH ACCA MANUAL N, TABLE 1A: OUTDOOR- 90
 DB, 78 WB.
 3) M1.1: REFERENCE SECTION 301.15 FBC-14 MECHANICAL AND
 PROVIDE THE DESIGN WIND PRESSURES FOR THE ROOF TOP
 MIAMI TECH CU AND CU BRACKET INSTALLATION. SUBMIT TWO
 COPIES OF A CURRENT FLORIDA PRODUCT APPROVAL FOR THE
 BRACKET REVIEWED AND APPROVED BY THE ENGINEER OF
 RECORD. THE ENGINEER SHALL CIRCLE, HIGHLIGHT, OR
 OTHERWISE MARK ALL DETAILS, NOTES, ANCHOR AND FASTENER
 SCHEDULES APPLICABLE TO THE PROPOSED INSTALLATION.
 4) M4.1, VENTILATION CALCULATIONS: UPDATE THE ASHRAE
 62.1 REFERENCE TO 2010. REFER TO SECTION 809.2 FBC-14
 EXISITING BUILDING CODE AND SHOW COMPLIANCE- ALTERED
 EXISTING SYSTEMS.
 IN MECHANICALLY VENTILATED SPACES, EXISTING MECHANICAL
 VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
 EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER
 MINUTE (CFM) (0.0024 M3/S) PER PERSON OF OUTDOOR AIR
 AND NOT LESS THAN 15 CFM (0.0071 M3/S) OF VENTILATION
 AIR PER PERSON; OR NOT LESS THAN THE AMOUNT OF
 VENTILATION AIR DETERMINED BY THE INDOOR AIR QUALITY
 PROCEDURE OF ASHRAE 62.
 5) COMMISSSIONING OF THE BUILDING MECHANICAL AND
 ELECTRICAL POWER AND LIGHT SYSTEMS ARE REQUIRED IN
 ACCORDANCE WITH SECTION C408 FBC-14 ENERGY COMPLIANCE.
 PLEASE PROVIDE A NARRATIVE ON THE PLAN DESCRIBING THE
 PROPOSED COMMISSIONING PROCEDURE AS OUTLINED IN SECTION
 C408.
  
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER