Plan Review Notes For Permit 15080378 |
Permit Number |
15080378 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-10-05 18:49:26 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE | | ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH | | REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE | | REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED | | SHALL BE RESUBMITTED FOR ANOTHER REVIEW. | | | | 1. CORRECT ENLARGED INSET 3, ROUTING OF ELECTRICAL VS. | | IT WIRE LINES. | | 2. NIGHT LIGHTING OR EMERGENCY LIGHT IS NOT CLEARLY | | DEFINED. | | 3. INDICATE THE LOCATION OF THE ELECTRICAL PANELS AND | | THE STEP DOWN TRANSFORMER. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED SHEETS. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | |
|