2015-08-25 07:02:21BUILDING PLAN REVIEW
 W. P. B. PERMIT:15080378
 ADD: 777 S. FLAGLER DR. SUITE # 1001E
 CONT: BUTLER
 TEL: (561)832-9700
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W
 * 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION,
  
 2014EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. AUGUST 25/2015
 ACTION: DENIED
  
 1) SHEET A-2.2 ROOM 1006 ADAPTABLE: PLEASE REVIEW THE
 2014 FL ACCESSIBLITY CODE RESTROOMS IN PRIVATE OFFICES
 AND WHEN THE EXCEPTION CAN BE APPLIED. THIS CODE IS
 CODE ARTICLE SPECIFIC. NOTE SECTION 603 .2.3 DOOR SWING
 EXCEPTION # 1 IS SPECIFIC TO TOLIET ROOMS WITHIN
 PRIVATE OFFICES, THE DOOR CAN SWING INTO RESTROOMS IN
 PRIVATE OFFICE.
  
 1A) THE CODE IS ALSO SPECIFIC TO THE REQUIRED OVERLAP
 IN 604.3.2. THE CODE DOES NOT GIVE ANY EXCEPTIONS.
 PLEASE NOTE THE CODE DOES ALLOW FOR
 THE TOLIET SEAT HEIGHT NOT NEEDING TO BE 17- TO 19
 INCHES WITH THE EXCEPTION TOLIET ROOMS IN PRIVATE
 OFFICES 604.4.
  
 1B) THE CODE DOES ALLOW FOR NOT INSTALLING GRAB BARS IN
 A PRIVATE OFFICE BUT THE REINFORCEMENT THAT IS REQUIRED
 BY 604.5 DOES NEED TO BE INSTALLED, PLEASE PROVIDE A
 DETAIL SHOWING CODE COMPLIANCE WITH 604.5 & 609.8
 STRUCTURAL STRENGTH OF 250 LBS WHEN APPLIED AT ANY
 POINT OF THE GRAB BAR.
  
 2) SHEET M2.2 INDICATES THE USE OF A WALL MOUNTED MIAMI
 TECH WIND RATED CONDENSING UNIT BRAKET AND STAND.
 PLEASE PROVIDE A PRODUCT APPROVAL OR ENGINEERING FOR A
 SITE SPECIFIC USE.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (G) PRE-ENGINEERED A/C STANDS
  
 3) 2014 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4) 2014 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4.5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  