2015-09-10 13:39:59 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE |
| CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW. |
| |
| 1. PER NFPA 72 SECTION 17.14.6, YOU SHALL HAVE A MANUAL |
| PULL STATION WITHIN 5' OF THE EXIT. THERE IS NO PULL |
| STATION BY THE EXIT IN THE RECEPTION AREA. IF THIS |
| SYSTEM IS EXEMPT FROM THIS REQUIREMENT DUE TO BEING A |
| FULLY SPRINKLED BLDG. YOU SHALL STATE SO ON THE PLANS. |
| 2. PER FBC-C SECTION 907.1.2, THE SHOP DRAWINGS SHALL |
| INCLUDE CONDUCTOR TYPE AND SIZE ALONG WITH VOLTAGE DROP |
| CALCS. |
| 3. THIS SAME SECTION REQUIRES THAT YOU SUBMIT |
| MANUFACTURERS SPEC SHEETS FOR ALL EQUIPMENT AND DEVICES |
| BEING USED ON THE SYSTEM. YOU TRIED TO COMPLY WITH THIS |
| BY SENDING LITERATURE ON A POWER SUPPLY BUT THIS POWER |
| SUPPLY DIFFERS FROM THE ONE INDICATED ON THE DRAWINGS. |
| 4. WHILE AT IT, YOU MAY WANT TO EDIT THE HEADING LABEL |
| ON THE CURRENT DRAW CHART TO READ BOTH ALARM & NON |
| ALARM CURRENT DRAWS. |
| 5. THE RISER DIAGRAM REFLECTS THE MAIN FACP AND AN |
| EXISTING NAC PANEL BUT IT FAILS TO INCLUDE THE NEW |
| POWER SUPPLY INDICATED PER YOUR SUBMITTED SPEC SHEET |
| AND LOCATED IN THE WIRE ROOM. YOU SHALL INDICATE THE |
| LOCATIONS OF THE FACP AND ALL POWER SUPPLIES HAVING |
| ANYTHING TO DO WITH THIS PORTION OF THE SYSTEM. |
| 6. I COULDN'T HELP BUT NOTICE THAT YOU MAKE REFERENCE |
| TO NFPA 2, SECTION 5.14.5.8. PLEASE HELP ME UNDERSTAND |
| WHAT DOE HYDROGEN HAVE TO DO WITH THIS PROJECT. |
| FURTHERMORE, HELP ME FIND THAT SECTION. MY VERSION OF |
| THIS BOOK DOES NOT GO UP THAT HIGH. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |