2015-08-13 18:46:59RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- METAL ROOFING PRODUCT APPROVAL FL11175-R2 SUBMITTED:
 DESIGN PRESSURES SHOWN ON PAGE 3 OF 17 DON'T MEET THE
 DESIGN PRESSURES FOR THE ROOF ZONE #3 ON THE MAIN HOUSE
 AS REQUIRED BY SEC. R301. THE DESIGN PRESSURES SHOWN ON
 THE SELECTED ASSEMBLY ARE OK FOR ROOF ZONES #1 (-71
 PSF) AND #2 (-93.5 PSF). THE DESIGN PRESSURES FOR ROOF
 ZONE # 3 ON A 6:12 PITCH WITH A MEAN ROOF HEIGHT OF 25'
 ON A BUILDING EXPOSURE "C" IS GREATER THAN -93.5 PSF
 (SEE TABLE R301.2(2). NEED TO SELECT ANOTHER ASSEMBLY
 THAT MEETS THE DESIGN PRESSURES OF ALL ROOF ZONES
 INCLUDING ZONE #3 OR PROVIDE ANOTHER PRODUCT APPROVAL
 THAT DOES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712