Plan Review Notes For Permit 15080359 |
Permit Number |
15080359 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-08-12 05:52:47 | 1) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF ALL GAS | | APPLIANCES. WPB AMEND. TO FBC SEC. 107.2.1. | | 2) INDICATE ALL TYPES OF PIPING THAT IS BEING INSTALLED | | IN THIS SYSTEM(METALLIC, CSST, ETC). I CANNOT REVIEW | | THIS PLAN FOR COMPLIANCE WITHOUT KNOWING THE TYPE OF | | PIPE MATERIAL BEING INSTALLED. | | 3) IF THE RANGE AND DRYER ARE NEW, SUBMIT | | MANUFACTURER'S SPECIFICATION SHEETS FOR THE APPLIANCES. | | ALL GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE | | 2014 FBC-RESIDENTIAL SEC. G 2404.3. | | 4) NOTE ON THE PLANS THE APPLICABLE SIZING TABLES USED | | FOR THE SIZING OF THE GAS SYSTEM. REFER TO THE 2014 | | FBC-RESIDENTIAL SEC.G2414. | | 5) SHOW THE LOCATION OF ALL STEP-DDOWN REGULATORS ON | | THE DRAWING. WPB AMEND. TO FBC SEC. 107.2.1. | | 6) THE MANUFACTURER'S INSTALLATION MANUAL FOR ALL GAS | | APPLIANCES SHALL BE ON THE JOBSITE FOR INSPECTION.2014 | | FBC-RESIDENTIAL SEC.G2408.1. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|