2015-08-26 11:24:29 | 705 NORTH OLIVE AVENUE - PHASED OCCUPANCY REQUEST |
| TRACKING #15080344 |
| MASTER #14030096 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| NOTE: ALL FIRE AND LIFE SAFETY SYSTEMS SHALL BE |
| INSPECTED, TESTED AND APPROVED PRIOR TO OCCUPANCY. A |
| "FIRE WATCH" IS NOT AN AVAILABLE OPTION FOR ALLOWING |
| OCCUPANCY. |
| |
| PROVIDE AN ADDRESS ON THE PLANS. |
| |
| PLANS AFFECTING THE FIRE AND LIFE SAFETY DESIGN WILL |
| NEED TO BE SIGNED/SEALED OR AT LEAST REVIEWED AND |
| STAMPED BY THE DESIGN PROFESSIONAL ACCEPTING |
| RESPONSIBILITY FOR THE MODIFIED DESIGN. |
| |
| STAIR #6 DISCHARGES INTO THE CONSTRUCTION STAGING AREA. |
| |
| FIRE ALARM CONTROL PANEL IS NOT LOCATED IN THE |
| "COMPLETED" PORTION OF THE BUILDING BUT IS LOCATED IN |
| THE HEART OF THE SECTOR B CONSTRUCTION ZONE. EXPLAIN |
| HOW THE FIRE ALARM SYSTEM WIRING WILL BE PROTECTED AND |
| THE INTEGRITY WILL BE MAINTAINED FOR THE WIRING THAT IS |
| BEING ROUTED THROUGH THE CONSTRUCTION ZONE TO BE |
| CONNECTED TO THE FACP. |
| |
| DETAILED DESCRIPTIONS AND PHASING DRAWINGS ARE NEEDED |
| FOR THE FIRE ALARM AND FIRE SPRINKLER/PUMP SYSTEMS. |
| |
| TESTING OF THE FIRE ALARM SYSTEM IN SECTORS B & C WILL |
| INITIATE THE GENERAL FIRE ALARM IN SECTOR A THAT MAY |
| LAST FOR SEVERAL HOURS AND BE CONDUCTED OVER SEVERAL |
| DAYS. HOW WILL RESIDENTS KNOW THE DIFFERENCE BETWEEN |
| TEST ALARMS AND TRUE ALARMS? |
| |
| THE PLANS INDICATE THE BARRIER WALLS ARE TO HAVE |
| SIGNAGE STATING, "NO ENTRY ALLOWED, CONSTRUCTION |
| PERSONNEL ONLY." INDICATE HOW WILL THIS WILL BE |
| REGULATED AND ENFORCED? |
| |
| INDICATE HOW FIRE DEPARTMENT VEHICLE ACCESS TO THE 20 |
| FOOT WIDE FIRE LANE WILL BE MAINTAINED ON EUCALYPTUS |
| STREET AND 6TH STREET DURING CONSTRUCTION ACTVITIES |
| WITH HALF THE BUILDING POTENTIALLY OCCUPIED AND THE |
| OTHER HALF UNDER CONSTRUCTION. |
| |
| JIM WALKER & WESLEY JOLIN |
| FIRE MARSHAL'S OFFICE |
| WEST PALM BEACH FIRE RESCUE |
| [email protected] |
| (561) 805-6730 |
| |