Plan Review Notes For Permit 15080270 |
Permit Number |
15080270 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-10-27 14:07:12 | PLAN | | REVIEW COMMENTS | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING | | EQUIPMENT AND APPLIANCES SHALL BE SIZED BASED ON | | BUILDING LOADS CALCULATED IN ACCORDANCE WITH ACCA | | MANUAL J OR OTHER APPROVED HEATING AND COOLING | | CALCULATION METHODOLOGIES. THE EQUIPMENT SIZING | | CALCULATIONS THAT WERE SUBMITTED HAVE AN INFLATED | | OCCUPANT LOAD OF 32 FOR THE FIRST FLOOR AND 16 FOR THE | | SECOND FLOOR. PLEASE CORRECT. | | | | 2) FBC ENERGY CONSERVATION SECTIONS R101.5.1.1.1 OR | | R101.5.1.1.2. THE ENERGY COMPLIANCE FORMS THAT WERE | | SUBMITTED HAVE THE WRONG ORIENTATION. THE 3' X 8'-8" | | FRONT DOOR FACES NORTH PER THE PLANS AND THE | | CALCULATIONS HAVE IT FACING EAST. THE OCCUPANT LOAD IS | | ALSO INCORRECT. THERE ARE 10 OCCUPANTS SPECIFIED FOR | | THE FIRST FLOOR AND 6 OCCUPANTS FOR THE SECOND FLOOR. | | |
|