2015-10-27 14:07:12PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT AND APPLIANCES SHALL BE SIZED BASED ON
 BUILDING LOADS CALCULATED IN ACCORDANCE WITH ACCA
 MANUAL J OR OTHER APPROVED HEATING AND COOLING
 CALCULATION METHODOLOGIES. THE EQUIPMENT SIZING
 CALCULATIONS THAT WERE SUBMITTED HAVE AN INFLATED
 OCCUPANT LOAD OF 32 FOR THE FIRST FLOOR AND 16 FOR THE
 SECOND FLOOR. PLEASE CORRECT.
  
 2) FBC ENERGY CONSERVATION SECTIONS R101.5.1.1.1 OR
 R101.5.1.1.2. THE ENERGY COMPLIANCE FORMS THAT WERE
 SUBMITTED HAVE THE WRONG ORIENTATION. THE 3' X 8'-8"
 FRONT DOOR FACES NORTH PER THE PLANS AND THE
 CALCULATIONS HAVE IT FACING EAST. THE OCCUPANT LOAD IS
 ALSO INCORRECT. THERE ARE 10 OCCUPANTS SPECIFIED FOR
 THE FIRST FLOOR AND 6 OCCUPANTS FOR THE SECOND FLOOR.
  