Plan Review Notes
Plan Review Notes For Permit 15080270
Permit Number 15080270
Review Stop G
Sequence Number 2
Notes
Date Text
2015-10-29 09:22:341) SUBMIT CALCULATIONS FOR COMBUSTION AIR. 2ND REQUEST.
 2014 FBC-RES. SEC. G2407.
 2) THE TOTAL BTU LOAD I HAVE CALCULATED FOR THIS SYSTEM
 BASED ON THE BTU LOAD SHOWN IS 1,103,000 BTU'S. REVISE
 TOTAL BTU LOAD ON THE PLAN.
 3) BASED ON THE TOTAL BTU LOAD OF THE LOW PRESSURE
 SYSTEM AND THE DISTANCE TO THE MOST REMOTE OUTLET (114
 FT. ) THE GALVANIZED LINE FROM THE REGULATOR SHALL BE A
 MINIMUM OF 2 INCHES IN SIZE UP TO THE FIRST TRANSITION
 TO CSST PER TABLE G2413.4 (1) OF 2014 FBC-RES.
 4) THE 10 FOOT SECTION OF CSST SHALL BE 2", NOT 1 1/4"
 AS SHOWN PER TABLE G 2413.4 (5) OF 2014 FBC-RES.
 5) THE 60 FOOT SECTION OF CSST SHALL BE 2", NOT 1 1/4 "
 PER 2014 FBC-RES. GAS TABLE G 2413.4 (5) OF 2014
 FBC-RES.
 6) THE SIZE OF THE CSST TO THE TANKLESS WATER HEATER IN
 THE MASTER BATH SHALL BE 1 1/4" PER 2014 FBC-RES. TABLE
 G2413.4 (5) AND THE GALVANIZED SHALL BE 1 1/4" PER
 TABLE G2413.4 (1).
 7) THE SIZE OF THE GALVANIZED LINE TO THE POOL HEATER
 SHALL BE 1 1/2" PER 2014 FBC-RES.TABLE G2413.4 (1) AND
 THE CSST SHALL BE 2" PER TABLE G2413.4 (5).
 8) SUBMIT TWO COPIES OF OF MANUFACTURER'S
 SPECIFICATIONS FOR ALL GAS APPLIANCES. THE ONLY SPECS
 SUBMITTED WERE FOR THE FIREPLACE. APPLIANCES SHALL BE
 LISTED AND LABELED PER 2014 FBC-RES. SEC. G2404.3.
 9) SHOW THE CORRELATING EHD OF THE CSST TO ENSURE
 CORRECT SIZING.
  
 I SUGGEST YOU CALL TO MAKE AN APPOINTMENT TO GO OVER
 THE GAS DRAWING.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  