2015-08-20 04:14:49THE SUBMITTED SANITARY RISER IS NOT TO CODE. THE
 FOLLOWING DEFICIENCIES ARE NOTED:
 1) THE SANITARY RISER AS DRAWN DOES NOT CORRELATE WITH
 THE FIRST AND SECOND FLOORS FIXTURE LOCATION LAYOUT.
 THE LAYOUT OF THE FIXTURES ON THE RISER SHALL CORRELATE
 WITH THE FLOOR PLAN.WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE LAUNDRY SINK SHALL BE STACKED AND VENTED PER
 FBC-R SEC.P3101.2
 3) WASHING MACHINE NOT PERMITTED ON WET VENT (AS
 DRAWN).FBC-R SEC. P3108.1.
 4) THE NUMBER AND TYPE OF FIXTURES ALLOWED ON WET VENT
 ARE EXCEEDED.
  
 SUBMIT A REVISED SANITARY RISER THAT IS CODE COMPLIANT.
  
 PLUMBING PLAN REVIEW