Plan Review Notes For Permit 15080270 |
Permit Number |
15080270 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-08-20 04:14:49 | THE SUBMITTED SANITARY RISER IS NOT TO CODE. THE | | FOLLOWING DEFICIENCIES ARE NOTED: | | 1) THE SANITARY RISER AS DRAWN DOES NOT CORRELATE WITH | | THE FIRST AND SECOND FLOORS FIXTURE LOCATION LAYOUT. | | THE LAYOUT OF THE FIXTURES ON THE RISER SHALL CORRELATE | | WITH THE FLOOR PLAN.WPB AMEND. TO FBC SEC. 107.2.1. | | 2) THE LAUNDRY SINK SHALL BE STACKED AND VENTED PER | | FBC-R SEC.P3101.2 | | 3) WASHING MACHINE NOT PERMITTED ON WET VENT (AS | | DRAWN).FBC-R SEC. P3108.1. | | 4) THE NUMBER AND TYPE OF FIXTURES ALLOWED ON WET VENT | | ARE EXCEEDED. | | | | SUBMIT A REVISED SANITARY RISER THAT IS CODE COMPLIANT. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | | | | | |
|