2015-09-25 18:09:56 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING | | EQUIPMENT AND APPLIANCES SHALL BE SIZED BASED ON | | BUILDING LOADS CALCULATED IN ACCORDANCE WITH ACCA | | MANUAL J OR OTHER APPROVED HEATING AND COOLING | | CALCULATION METHODOLOGIES. PROVIDE TWO SETS OF | | EQUIPMENT SIZING CALCULATIONS. | | | | 2) THE SUPPLY DUCT SIZES FOR THE LAUNDRY AND HER WALKIN | | CLOSET ON THE FIRST FLOOR ARE MISSING FROM THE PLANS. | | FBC 107.2.1 | | | | 3) SUBMIT TWO SETS OF ENERGY COMPLIANCE FORMS AS | | REQUIRED BY FBC ENERGY CONSERVATION SECTIONS | | R101.5.1.1.1 OR R101.5.1.1.2 | | |
|