Plan Review Notes
Plan Review Notes For Permit 15080270
Permit Number 15080270
Review Stop M
Sequence Number 1
Notes
Date Text
2015-09-25 18:09:56PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT AND APPLIANCES SHALL BE SIZED BASED ON
 BUILDING LOADS CALCULATED IN ACCORDANCE WITH ACCA
 MANUAL J OR OTHER APPROVED HEATING AND COOLING
 CALCULATION METHODOLOGIES. PROVIDE TWO SETS OF
 EQUIPMENT SIZING CALCULATIONS.
  
 2) THE SUPPLY DUCT SIZES FOR THE LAUNDRY AND HER WALKIN
 CLOSET ON THE FIRST FLOOR ARE MISSING FROM THE PLANS.
 FBC 107.2.1
  
 3) SUBMIT TWO SETS OF ENERGY COMPLIANCE FORMS AS
 REQUIRED BY FBC ENERGY CONSERVATION SECTIONS
 R101.5.1.1.1 OR R101.5.1.1.2
  