2015-08-17 16:44:30 | BUILDING PLAN REVIEW |
| REVISION: 15080255 |
| PERMIT:14071105 |
| ADD: 1517 CAMERON SAMUEL LN. |
| CONT: KAST |
| TEL: (561)346-4994 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 1ST REVIEW |
| DATE: MON. AUG.17/2015 |
| ACTION: DENIED |
| |
| ROOF SUBMITTALS; |
| |
| 1) FLAT ROOF: |
| 1A) THE ENGINEERING FROM FORENSIC ENGINEERING IS A COPY |
| NOT THE SIGNED SEALED ORIGINALS. 61G15-30.003 |
| ENGINEERING DOCUMENT CLASSIFICATION. ENGINEERS SHALL |
| LEGIBLY INDICATE THEIR NAME AND BUSINESS ADDRESS, ON |
| ENGINEERING DOCUMENTS. ENGINEERING DOCUMENTS WHICH ARE |
| ISSUED FOR PRELIMINARY OR CONCEPTUAL USE, SHALL CLEARLY |
| NOTE THE INTENDED PURPOSE OF SUCH DOCUMENTS. |
| |
| 1B) THE FORENSIC ENGINEERING SHEET WIND DESIGN CRITERIA |
| IS 170 MPH AND EXPOSURE D. PLEASE REVIEW THE STRUCTURAL |
| SHEET S6 THE WIND DESIGN |
| IS 180 MPH, EXPOSURE C RISK CATEGORY III. PLEASE |
| RE-CALCULATE THE PRESSURES AND ANCHORING TO THE CORRECT |
| CRITERIA. 2010 FBC-B 2010 FBC-B 1609.1.1 DETERMINATION |
| OF WIND DESIGN- CHAPTER 6 OF ASCE 7-10. |
| |
| 2) SLOPED ROOFS METAL |
| 2A) THE ENGINEERING SHEET FROM GFA CARLOS MERCADO P.E. |
| IS A COPY NOT THE SIGNED SEALED ORIGINALS. 61G15-30.003 |
| ENGINEERING DOCUMENT CLASSIFICATION. ENGINEERS SHALL |
| LEGIBLY INDICATE THEIR NAME AND BUSINESS ADDRESS, ON |
| ENGINEERING DOCUMENTS. ENGINEERING DOCUMENTS WHICH ARE |
| ISSUED FOR PRELIMINARY OR CONCEPTUAL USE, SHALL CLEARLY |
| NOTE THE INTENDED PURPOSE OF SUCH DOCUMENTS. |
| |
| 2B) PLEASE NOT THE GFA ENGINEEREING INCLUDES METAL ROOF |
| SYSTEMS FOR 2 BUILDINGS; |
| 1) CLUBHOUSE |
| 2) TOWER ROOF |
| |
| PLEASE NOTE THERE WILL BE (2) DESIGN CRITERIA REQUIRED. |
| THE CLUBHOUSE IS DESIGNED TO 180 MPH EXPOSURE C |
| BUILDING CATEGORY III, WHERE AS THE TOWER ROOF IS ONLY |
| A BUILDING CATEGORY II THE WIND DESIGN AT 170 MPH. |
| PLEASE ALSO NOTE THERE WILL BE 2 DIFFERENT MEAN ROOF |
| HEIGHTS INVOLVED. |
| 2010 FBC-B 2010 FBC-B 1609.1.1 DETERMINATION OF WIND |
| DESIGN- CHAPTER 6 OF ASCE 7-10. PLEASE RECALCULATE TO |
| THE APPROPRIATE WIND DESIGN FOR EACH OF THE BUILDINGS. |
| |
| 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |