2015-10-20 14:32:21 | ****CORRECTIONS**** |
| REVISED 11/9/15 (SEE NEW COMMENT) |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. OPENING DIMENSIONS AND NOTES UNDER "GENERAL SCOPE OF |
| WORK" ARE TOO SMALL TO BE LEGIBLE. INCREASE FONT SIZE |
| FOR THESE ITEMS, FBC 107. |
| |
| 2. REVISE THE INSTALLATION SCHEDULE AS FOLLOWS: |
| |
| A. SHUTTER MOUNTING CONNECTION TYPE SHOULD CORRELATE |
| WITH THE ANCHOR CHARTS IN THE PRODUCT APPROVAL; FOR |
| EXAMPLE, SEE SHEET 11. SECTIONS (CONNECTION TYPES) ARE |
| NAMED 1(TOP), 1(BOTTOM), 2(TOP), 2(BOTTOM), ETC. |
| |
| B. IF INSTALLATION IS VERTICAL, SPANS SHOULD BE THE |
| DIMENSION ANCHOR TO ANCHOR, SO SHOULD BE OPENING HEIGHT |
| PLUS EDGE DISTANCE TOP AND BOTTOM. SPANS APPEAR TO |
| CORRELATE WITH THE HORIZONTAL DIMENSION, THE WIDTH. |
| |
| WITHOUT THE CONNECTION TYPE AND SPAN, IT IS NOT |
| POSSIBLE TO DETERMINE CODE COMPLIANCE. |
| |
| 3. WHEN RESUBMITTING, REVISE THE APPLICATION TO BE |
| CONSISTENT WITH THE SCOPE OF WORK STATED (STILL STATES |
| WINDOW AND DOOR REPLACEMENT). |
| |
| 4. WHEN RESUBMITTING, COLLATE TWO IDENTICAL SETS OF |
| PERMIT DOCUMENTS FOR PERMIT ISSUANCE. |
| |
| ***NEW COMMENT*** |
| |
| 5. RESUBMITTAL FORM STATES THAT "EXISTING WINDOWS TO |
| REMAIN." WINDOWS WERE REPLACED WITHOUT A PERMIT AND |
| THEREFORE A CODE CASE WAS GENERATED. THE WINDOWS |
| INSTALLED WITHOUT PERMIT REQUIRE A PERMIT. THEY ARE NOT |
| CONSIDERED "EXISTING" AS THEY HAVE NOT BEEN PERMITTED |
| AND INSPECTED AND THEY DO NOT COMPLY WITH FBC |
| REQUIREMENTS (LACKING IMPACT PROTECTION). |
| |
| |
| |
| |
| |
| |