Plan Review Notes
Plan Review Notes For Permit 15080183
Permit Number 15080183
Review Stop B
Sequence Number 1
Notes
Date Text
2015-08-10 09:10:42****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 5TH EDITION 2014
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 SAM 3 90 SPEC SHEETS, STC & IIC TEST REPORTS PROVIDED
  
 NOTE - THE MANUFACTURER HAS BEEN CONTACTED VIA EMAIL
 (CONTRACTOR CC'D) ABOUT POSSIBLE USE OF SUPERSAM 125.
 TEST REPORTS HAVE BEEN PROVIDED FOR THIS PRODUCT BUT A
 LETTER ON LETTERHEAD IS REQUIRED FOR THE IIC (ASTM E
 492) STATING THAT THE ASSEMBLY TESTED (QUARRY TILE,
 MORTAR BED, OVER 6" SLAB) IS EQUIVALENT TO AN 8.25" (OR
 THINNER) SLAB, CERAMIC TILE. IF PROVIDED, THIS LETTER
 WILL BE PUT ON FILE.
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
  
 THE TEST REPORT PROVIDED INCLUDES A DROPPED INSULATED
 GYPSUM BOARD CEILING ASSEMBLY, CASTELE TRAVERTINE TILE
 IN A MORTAR BED. THIS IS NOT CONSISTENT WITH THE
 PROPOSED INSTALLATION.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
  
 THE TEST REPORT PROVIDED INCLUDES A DROPPED INSULATED
 GYPSUM BOARD CEILING ASSEMBLY, CASTELE TRAVERTINE TILE
 IN A MORTAR BED. THIS IS NOT CONSISTENT WITH THE
 PROPOSED INSTALLATION.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 4. TO AVOID MULTIPLE PLAN REVIEWS, A PRELIMINARY REVIEW
 WILL BE DONE VIA EMAIL UNDER THE FOLLOWING CONDITIONS:
  
 QUALIFIER IS TO REVIEW THE COMMENT LIST AND DOCUMENTS
 PROPOSED. FOR THE ACOUSTICAL (STC & IIC) TESTS,
 QUALIFIER TO HIGHLIGHT THE ASSEMBLY (SPECIFICALLY WHERE
 NO DROPPED CEILING WAS USED IN THE TEST) AS WELL AS THE
 TEST RESULT.
 FOR THE FLAME SPREAD, QUALIFIER IS TO HIGHLIGHT THE
 TEST STANDARD (SHOULD BE EITHER ASTM E 84 OR UL 723)
 AND TEST RESULT.
  
 DUE TO CURRENT WORK LOAD AND LACK OF TIME TO MAINTAIN
 TARGET TURNAROUND TIMES, IF APPLICANT IS UNABLE TO
 COMPLY WITH ITEM 4, THE COURTESY REVIEW VIA EMAIL WILL
 NOT BE DONE. PLEASE RESUBMIT AT THE BUILDING DIVISION
 COUNTER.
  