2015-08-27 08:55:39PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE DUCT SIZE, GRILL SIZE AND CFMS FOR THE
 NEW SUPPLY TO THE OFFICE SPACE. FBC 107.2.1
  
 2) SUBMIT THE CURRENT ENERGY FORM. FORM 402-2010 WAS
 SUBMITTED AND FORM 402-2014 IS REQUIRED. 2014 FBC
 ENERGY CONSERVATION SECTION R101.5.1.1.1
  
 3) FORM 402-2014 IS REQUIRED TO BE SIGNED AND DATED BY
 THE OWNER/AGENT AND THE PREPARER. 2014 FBC ENERGY
 CONSERVATION SECTION R101.5.1.1.1
  
  