Plan Review Notes
Plan Review Notes For Permit 15080161
Permit Number 15080161
Review Stop B
Sequence Number 1
Notes
Date Text
2015-08-27 08:59:00PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) BASED ON FBC - R301.2.1.4.3, THE PROJECT IS LOCATED
 IN EXPOSURE CATEGORY D. THE PLANS SPECIFY EXPOSURE
 CATEGORY C.
  
 2) REVISE THE COMPONENT AND CLADDING DESIGN PRESSURES
 TO EXPOSURE CATEGORY D. FBC-R 301.1
  
 3) THE ENERGY CODE (FORM R402-2014) REQUIRES THE WALL
 INSULATION TO BE R-13. THE WALL SECTION SPECIFIES R-11.
  
 4) UPDATE THE CODE EDITIONS AS FOLLOWS. THESE ARE THE
 EDITIONS REFERENCED IN THE 2014 FBC. THE 2011 NATIONAL
 ELECTRICAL CODE, NFPA 101 - 2012, AND THE 2014 FIRE
 PREVENTION CODE.
  
 5) THE WALL SECTION SPECIFIES ONLY ONE LAYER OF 30#
 FELT ON THE EXTERIOR WALL UNDER THE LATH AND STUCCO.
 R703.6.3 WATER-RESISTIVE BARRIERS SHALL BE INSTALLED AS
 REQUIRED IN SECTION R703.2 AND, WHERE APPLIED OVER
 WOOD-BASED SHEATHING, SHALL INCLUDE A WATER-RESISTIVE
 VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST
 EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE
 INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH
 THAT EACH LAYER PROVIDES A SEPARATE CONTINUOUS PLANE
 AND ANY FLASHING (INSTALLED IN ACCORDANCE WITH SECTION
 R703.8) INTENDED TO DRAIN TO THE WATER-RESISTIVE
 BARRIER IS DIRECTED BETWEEN THE LAYERS.
  
 6) FBC - R704 INSPECTION FOR TERMITES IN ORDER TO
 PROVIDE FOR INSPECTION FOR TERMITE INFESTATION,
 CLEARANCE BETWEEN EXTERIOR WALL COVERINGS AND FINAL
 EARTH GRADE ON THE EXTERIOR OF A BUILDING SHALL NOT BE
 LESS THAN 6 INCHES (152 MM).
  
 7) FBC - R703.6.2.1 WEEP SCREEDS. A MINIMUM 0.019-INCH
 (0.5 MM) (NO. 26 GALVANIZED SHEET GAGE),
 CORROSION-RESISTANT WEEP SCREED OR PLASTIC WEEP SCREED,
 WITH A MINIMUM VERTICAL ATTACHMENT FLANGE OF 31/2
 INCHES (89 MM) SHALL BE PROVIDED AT OR BELOW THE
 FOUNDATION PLATE LINE ON EXTERIOR STUD WALLS IN
 ACCORDANCE WITH ASTM C 926. THE WEEP SCREED SHALL BE
 PLACED A MINIMUM OF 4 INCHES (102 MM) ABOVE THE EARTH
 OR 2 INCHES (51 MM) ABOVE PAVED AREAS AND SHALL BE OF A
 TYPE THAT WILL ALLOW TRAPPED WATER TO DRAIN TO THE
 EXTERIOR OF THE BUILDING. THE WEATHER-RESISTANT BARRIER
 SHALL LAP THE ATTACHMENT FLANGE. THE EXTERIOR LATH
 SHALL COVER AND TERMINATE ON THE ATTACHMENT FLANGE OF
 THE WEEP SCREED.
  
 9) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD. FBC 107.3.4
  
 10) SUBMIT TWO COPIES OF COVERSHEETS OR OTHER DOCUMENTS
 THAT SPECIFY THE FL NUMBER FOR THE JELD-WEN FRENCH
 DOORS. FBC 107.2.1
  
  