2015-09-21 16:46:36****CORRECTIONS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA
 RESIDENTIAL CODE 2015 5TH EDITION
  
 SECOND REVIEW:
  
 1. ADDRESSED.
  
 2. FBC - R301.2.1.2 PROTECTION OF OPENINGS.
 WINDOWS IN BUILDINGS LOCATED IN WINDBORNE DEBRIS
 REGIONS SHALL HAVE GLAZED OPENINGS PROTECTED FROM
 WINDBORNE DEBRIS. GLAZED OPENING PROTECTION FOR
 WINDBORNE DEBRIS SHALL MEET THE REQUIREMENTS OF THE
 LARGE MISSILE TEST OF ASTM E 1996, ASTM E 1886, SSTD 12
 OR TAS 201, 202 AND 203 OR AAMA 506 REFERENCED THEREIN.
  
 3. PROVIDE TWO COPIES OF A PRODUCT APPROVAL NOA FOR
 WINDOWS USED. IF WINDOWS ARE NOT IMPACT WINDOWS PROVIDE
 SHUTTER SCHEDULE AND NOA'S.
  
 4. PLEASE SHOW THE ROOM USE OF THE NEW ROOM AND THE
 EXISTING ROOM THAT THE DOORWAY IS GOING TO BE BLOCKED
 OFF. NEW: NOW THAT THE EXISTING ROOM THAT HAS THE DOOR
 BLOCKED OFF IS SHOWN AS A BEDROOM. PLEASE SHOW HOW THIS
 ROOM WILL COMPLY WITH R-310 EMERGENCY ESCAPE AND RESCUE
 OPENINGS.
  
 5. ADDRESSED
  
 6. ADDRESSED
  
 7. ADDRESSED
  
 8. ADDRESSED
  
 9. SHOW WALL SHEATHING FASTENING METHOD.
  
  