Plan Review Notes For Permit 15080157 |
Permit Number |
15080157 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-09-10 10:20:59 | 1ST REVIEW: FBC 2014 5TH ED./NEC 2011 | | | | DEMONSTRATE COMPLIANCE WITH THE FOLLOWING SECTIONS: | | | | FBC-R 315.1 ? PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 | | FEET OF EACH SLEEPING ROOM, IF APPLICABLE. | | | | E4002.14 TAMPER-RESISTANT RECEPTACLES. | | IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15- | | AND 20-AMPERE RECEPTACLES SHALL BE LISTED | | TAMPER-RESISTANT RECEPTACLES. | | | | E3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. | | ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, | | 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS, | | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, | | BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS, | | HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED | | BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER | | INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | | | |
|