2015-09-08 17:07:41 | ****CORRECTIONS**** |
| |
| ART LANGE - BUILDING INSPECTOR |
| 561-805-6667 [email protected] |
| FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA |
| RESIDENTIAL CODE 2015 5TH EDITION |
| |
| 1. PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. |
| CALL 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE |
| PLAN AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE |
| RETURNED STAMPED WITH A COPY OF RECEIPT AS APPLICABLE. |
| |
| 2. FBC - R301.2.1.2 PROTECTION OF OPENINGS. |
| WINDOWS IN BUILDINGS LOCATED IN WINDBORNE DEBRIS |
| REGIONS SHALL HAVE GLAZED OPENINGS PROTECTED FROM |
| WINDBORNE DEBRIS. GLAZED OPENING PROTECTION FOR |
| WINDBORNE DEBRIS SHALL MEET THE REQUIREMENTS OF THE |
| LARGE MISSILE TEST OF ASTM E 1996, ASTM E 1886, SSTD 12 |
| OR TAS 201, 202 AND 203 OR AAMA 506 REFERENCED THEREIN. |
| |
| 3. PROVIDE TWO COPIES OF A PRODUCT APPROVAL NOA FOR |
| WINDOWS USED. IF WINDOWS ARE NOT IMPACT WINDOWS PROVIDE |
| SHUTTER SCHEDULE AND NOA'S. |
| |
| 4. PLEASE SHOW THE ROOM USE OF THE NEW ROOM AND THE |
| EXISTING ROOM THAT THE DOORWAY IS GOING TO BE BLOCKED |
| OFF. |
| |
| 5. SHOW ROOF INSULATION AND VENTING. |
| |
| 6. IS THIS EXISTING SLAB GOING TO BE POURED OVER. |
| |
| 7. NO A/C SHOWN ON PLANS. |
| |
| 8. PROVIDE WIND DESIGN CRITERIA COMPLYING WITH |
| R-301.2.1 |
| |
| 9. SHOW WALL SHEATHING FASTENING METHOD. |
| |
| NOTE: INSUFFICIENT INFORMATION SUBMITTED FOR A COMPLETE |
| PLAN REVIEW. |
| |
| |