Plan Review Notes
Plan Review Notes For Permit 15080157
Permit Number 15080157
Review Stop B
Sequence Number 1
Notes
Date Text
2015-09-08 17:07:41****CORRECTIONS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA
 RESIDENTIAL CODE 2015 5TH EDITION
  
 1. PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE.
 CALL 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED WITH A COPY OF RECEIPT AS APPLICABLE.
  
 2. FBC - R301.2.1.2 PROTECTION OF OPENINGS.
 WINDOWS IN BUILDINGS LOCATED IN WINDBORNE DEBRIS
 REGIONS SHALL HAVE GLAZED OPENINGS PROTECTED FROM
 WINDBORNE DEBRIS. GLAZED OPENING PROTECTION FOR
 WINDBORNE DEBRIS SHALL MEET THE REQUIREMENTS OF THE
 LARGE MISSILE TEST OF ASTM E 1996, ASTM E 1886, SSTD 12
 OR TAS 201, 202 AND 203 OR AAMA 506 REFERENCED THEREIN.
  
 3. PROVIDE TWO COPIES OF A PRODUCT APPROVAL NOA FOR
 WINDOWS USED. IF WINDOWS ARE NOT IMPACT WINDOWS PROVIDE
 SHUTTER SCHEDULE AND NOA'S.
  
 4. PLEASE SHOW THE ROOM USE OF THE NEW ROOM AND THE
 EXISTING ROOM THAT THE DOORWAY IS GOING TO BE BLOCKED
 OFF.
  
 5. SHOW ROOF INSULATION AND VENTING.
  
 6. IS THIS EXISTING SLAB GOING TO BE POURED OVER.
  
 7. NO A/C SHOWN ON PLANS.
  
 8. PROVIDE WIND DESIGN CRITERIA COMPLYING WITH
 R-301.2.1
  
 9. SHOW WALL SHEATHING FASTENING METHOD.
  
 NOTE: INSUFFICIENT INFORMATION SUBMITTED FOR A COMPLETE
 PLAN REVIEW.
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved