2015-08-10 14:28:48 | BUILDING PROVISO: | | DOORS 100, 100A & 105 TO HAVE ELECTRO-MAGNETIC LOCKS | | SHOW COMPLIANCE WITH: | | 2010 FBC-B 1008.1.9.8 ELECTROMAGNETICALLY LOCKED EGRESS | | DOORS. | | DOORS IN THE MEANS OF EGRESS IN BUILDINGS WITH AN | | OCCUPANCY IN GROUP A, B, E, M, R-1 OR R-2, | | AND DOORS TO TENANT SPACES IN GROUP A, B, E, M, R-1 OR | | R-2, SHALL BE PERMITTED TO BE | | ELECTROMAGNETICALLY LOCKED IF EQUIPPED WITH LISTED | | HARDWARE THAT INCORPORATES A BUILT-IN SWITCH | | AND MEET THE REQUIREMENTS BELOW: | | | | 1. THE LISTED HARDWARE THAT IS AFFIXED TO THE DOOR LEAF | | HAS AN OBVIOUS METHOD OF OPERATION | | THAT IS READILY OPERATED UNDER ALL LIGHTING CONDITIONS. | | | | 2. THE LISTED HARDWARE IS CAPABLE OF BEING OPERATED | | WITH ONE HAND. | | | | 3. OPERATION OF THE LISTED HARDWARE DIRECTLY INTERRUPTS | | THE POWER TO THE ELECTROMAGNETIC LOCK | | AND UNLOCKS THE DOOR IMMEDIATELY. | | | | 4. LOSS OF POWER TO THE LISTED HARDWARE AUTOMATICALLY | | UNLOCKS THE DOOR. | | | | 5. WHERE PANIC OR FIRE EXIT HARDWARE IS REQUIRED BY | | SECTION 1008.1.10, OPERATION OF THE LISTED | | PANIC OR FIRE EXIT HARDWARE ALSO RELEASES THE | | ELECTROMAGNETIC LOCK. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|