2015-09-21 16:58:06****CORRECTIONS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION/ FRC FLORIDA
 RESIDENTIAL CODE 2015 5TH EDITION
  
 SECOND REVIEW:
  
 1. PROVIDE A FLOOR PLAN AND WINDOW SCHEDULE SHOWING THE
 ROOM TYPE, SIZE, TYPE AND LOCATION OF ALL WINDOWS.
 INCLUDE DOORS IF THEY ARE GOING TO BE REPLACED. NOTE:
 DOORS WERE NOT INCLUDED ON THE PERMIT APPLICATION.
  
 2. PROVIDE PRESSURES AT OPENINGS. R-301.2
  
 3. COLLATE TWO COMPLETE SETS OF DOCUMENTS SUBMITTED.