2015-08-05 17:37:59RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC-5TH EDITION (2014)
  
 1- PROVIDE FASTENER WITHDRAWAL TEST (TAS 105 OR ANSI
 /SPRI FX-1) AS REQUIRED BY NOTE #9 OF FLORIDA PRODUCT
 APPROVAL FL1046-R7 SUBMITTED. PROVIDE 2 COPIES WITH
 ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 CHAPTER 471 F.S.
  
 2- BASED ON THE RESULTS OF THE FASTENER WITHDRAWAL TEST
 REQUIRED BY ITEM #1 ABOVE, PROVIDE SIGNED AND SEALED
 RAS 117 (OR FM LPDS 1-29) AS REQUIRED BY NOTE #7 OF
 FLORIDA PRODUCT APPROVAL FL1046-R7 SUBMITTED. PROVIDE 2
 COPIES WITH ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS
 REQUIRED BY CHAPTER 471 F.S.
  
 NOTE: ANY ROOF A/C EQUIPMENT REMOVAL REQUIRES SEPARATE
 PERMIT.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  
  