2015-09-23 14:38:30 | RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS. |
| CODE: FBC-5TH EDITION (2014). |
| |
| 1- BUILDING IS LOCATED IN FLOOD ZONE A5 WITH A BASE |
| FLOOD ELEVATION OF 7'-0". ACCORDING TO ELEVATION |
| CERTIFICATE ON CITY RECORDS THE FINISH FLOOR ELEVATION |
| OF THE GARAGE IS 6.6'. THE FINISHED FLOOR ELEVATION |
| NEEDS TO BE AT LEAST 6" ABOVE THE BASED FLOOR ELEVATION |
| (7'-6"MIN.) OR THE CONSTRUCTION OF THE NEW ADDITION |
| NEEDS TO COMPLY WITH ALL THE REQUIREMENTS OF SEC. R322 |
| OF FBC-RESIDENTIAL, 5TH EDITION (2014). COORDINATE WITH |
| ITEM #3(C) AND #3(D) BELOW. |
| |
| 2- SHEET A-1: |
| A) NEED TO SPECIFY CARBON MONOXIDE ALARMS WITHIN 10' OF |
| EACH SLEEPING ROOM AS REQUIRED BY SEC. R315 OF |
| FBC-RESIDENTIAL, 5TH EDITION (2014). |
| |
| B) REVISE THE GENERAL NOTES: REFERENCE THE CURRENT CODE |
| IN EFFECT 2014 NOT 2010. CHAPTER 553 F.S. |
| |
| C) SPECIFY FLOOD RESISTANT MATERIALS AS REQUIRED BY |
| SEC. R322.1.8. |
| |
| D) PROVIDE COMPLETE INFORMATION FOR THE FLOOD VENTS |
| SHOWING COMPLIANCE WITH SEC. R322.2.2. CHECK REQUIRED |
| NUMBER OF VENTS PER SIDE, LOCATION AND SIZE OF VENTS |
| REQUIRED. NOTE: COORDINATE WITH FLOOD VENT PRODUCT |
| APPROVAL. |
| |
| 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR FLOOD VENTS. NOTE: COORDINATE |
| WITH ITEM #3(D) ABOVE. |
| |
| 4- DESIGNER OF RECORD TO APPROVE FLOOD VENTS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. PLEASE |
| PLACE REVIEW STAMP ON THE COVER OF THE PRODUCT APPROVAL |
| NOT ON THE BACK. THIS WILL FACILITATE THE SCANNING OF |
| ALL DOCUMENTS. |
| |
| ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| ***PLEASE REPLACE AND REMOVE ANY REVISED DRAWING. |
| SUBMIT OLD COPIES FOR REFERENCE. |
| |