Plan Review Notes For Permit 15080090 |
Permit Number |
15080090 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2015-08-20 17:45:25 | HAVING FIRST BEEN APPROVED BY ZONING, I CAN APPROVED | | THE PERMIT WITH THE FOLLOWING PROVISOS | | PROVISOS FOR PERMIT 15080090 | | 1. ALL REPLACEMENT RECEPTACLES SHALL COMPLY WITH NEC | | 406.4 (D)(1) ? (D)(4) | | 2. OUTLET SPACING AS REFLECTED ON PLANS DOES NOT MEET | | MINIMUM SPACING REQUIREMENTS MANDATED IN NEC 210.52. IF | | ONLY REPLACING DEVICES W/O OPENING WALLS, OUTLETS MAY | | REMAIN AS THEY ARE; OTHERWISE FOLLOW MINIMUM | | REQUIREMENTS AS MARKED ON THE PLANS. | | 3. ALL CEILING LUMINAIRE OUTLETS SHALL BE LISTED TO | | SUPPORT 50 LB. PER NEC 314.27 | | 4. PANEL ?B? FOR DETACHED STRUCTURE SHALL BE GROUNDED | | AS INDICATED. | | |
|