2015-08-14 07:26:25 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 15080079 |
| ADD: 5402 EAST AVENUE |
| CONT: STUART & SHELBY |
| TEL: (561)637-7902 |
| E-MAIL:[email protected] |
| |
| 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION, |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. AUGUST 14/ 2015 |
| ACTION: DENIED |
| |
| 1) ARCHITECTURAL PLANS BY RICHARD WENSING ARCHITECT ARE |
| COPIES AND REDUCED IN SIZE. PLANS ARE COPYERIGHTED. |
| |
| 1A)PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN |
| CODE 61G16.003 ARCHITECTS. |
| |
| 1B) 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| SUBSTANTIAL PAPER. THE BUILDING OFFICIAL MAY ESTABLISH |
| THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS |
| AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO |
| ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE |
| SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, |
| OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT. |
| ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE |
| REQUIREMENTS OF FLORIDA STATUTES. |
| |
| 2)107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS: |
| OCCUPANCY TYPE |
| MINIMUM BUILDING TYPE |
| FIRE SPREINKLERED OR NOT |
| FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| AND OR CEILINGS MORE THAN 1STORY? |
| |
| 3) NOTE # 3 SCOPE OF WORK NOTE # 3 INDICATES THE |
| REMOVAL OF ACOUSTICAL CEILINGS AND THEN FRAMING IN NEW |
| AND HANGING DRYWALL CEILINGS AS REQUIRED BY CODE. NO |
| PLANS WERE SUPPLIED TO BE ABLE TO COMPLETE A REVIEW |
| WITH. NO MATERIALS, SPANS, NO INFORMATION. 107.3.5.1.1 |
| MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. 2014 FBC-B |
| TABLE 2508.1 ASTM C754; ASTM C1007, GA 216 & ASTM C840. |
| PLANS WILL NEED TO IDENTIFY THE DEFLECTION LIMITATION, |
| ALLOWABLE CEILING SPAN FOR TYPE OF FRAMING MEMBER, |
| IDENTIFY FRAMING MEMBERS, WILL THEY NEED STIFF BACKS, |
| GAUGE OF FRAMING MEMBERS, CENTERS OF FRAMING MEMBERS, |
| THE THICKNESS OF DRYWALL, ATTACHMENT, TYPE OF FASTENER, |
| SPACING, GAUGE OF FASTENER AND LENGTH OF FASTENER. |
| |
| NOTE DEPENDING ON THE A/C DUCTWORK LAYOUT, MAY REQUIRE |
| FIRE DAMPERS AND ACCESSIBLE PANELS. |
| |
| 4) NOTE # 4 ADD ADDITIONAL STUDS TO SHOWER AREAS AS |
| REQUIRED BY CODE. PLEASE PROVIDE THE SPACING OF STUDS, |
| TYPE OF MATERIALS USED, FOR TYPE OF BUILDING, |
| AND COMPLIANCE WITH 2014 FBC-B 2509.2 BASE FOR TILE. |
| NOTE: 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, SUCH |
| INFORMATION SHALL BE SPECIFIC, |
| AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION. |
| |
| 5) NOTE # 5. HHANG DEN-SHIED OR EQUAL. 2014 WEST PALM |
| BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| 1, ADMINISTRATION, SUCH INFORMATION SHALL BE SPECIFIC, |
| AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE |
| OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS |
| EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION. |
| |
| 6) NOTE # 9 INDICATES INSULATE FRAMED CEILING SPACES OF |
| GUEST ROOMS WITH R-30 BATT MATERIALS. PLEASE SHOW |
| COMPLIANCE WITH 2014 FBC-ENERGY C402.4.9.2 UNVENTED |
| DROPPED CEILING CAVITIES. |
| WHERE UNVENTED DROPPED CEILING CAVITIES OCCUR OVER |
| CONDITIONED SPACES THAT DO NOT HAVE AN AIR BARRIER |
| BETWEEN THE CONDITIONED AND UNCONDITIONED SPACE (SUCH |
| AS T-BAR CEILINGS), THEY SHALL BE COMPLETELY SEALED |
| FROM THE EXTERIOR ENVIRONMENT (AT THE ROOF PLANE) AND |
| ADJACENT SPACES BY A CONTINUOUS AIR BARRIER THAT IS |
| ALSO SEALED TO THE AIR BARRIER OF THE WALLS. IN THAT |
| CASE, THE ROOF ASSEMBLY SHALL CONSTITUTE BOTH THE UPPER |
| THERMAL ENVELOPE AND PRESSURE ENVELOPE OF THE BUILDING. |
| |
| |
| 6) NOTE # 12 INDICATE TO INSTALL EXIT AND EMERGENCY |
| LIGHTING AS REQUIRED. PLEASE PROVIDE A LIFE SAFETY |
| PLAN. |
| 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS: |
| OCCUPANCY TYPE |
| MINIMUM BUILDING TYPE |
| FIRE SPREINKLERED OR NOT |
| OCCUPANCY LOAD |
| GROSS |
| NET |
| MEANS OF EGRESS |
| EXIT ACCESS |
| EXIT |
| EXIT DISCHARGE |
| EMERGENCY LIGHTING |
| DERECTIONAL EXIT LIGHTS |
| EXIT LIGHTS |
| |
| 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |