2015-08-14 07:26:25BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15080079
 ADD: 5402 EAST AVENUE
 CONT: STUART & SHELBY
 TEL: (561)637-7902
 E-MAIL:[email protected]
  
 2014 FLORIDA BUILDING CODE W * 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION,
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. AUGUST 14/ 2015
 ACTION: DENIED
  
 1) ARCHITECTURAL PLANS BY RICHARD WENSING ARCHITECT ARE
 COPIES AND REDUCED IN SIZE. PLANS ARE COPYERIGHTED.
  
 1A)PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G16.003 ARCHITECTS.
  
 1B) 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER. THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO
 ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE
 SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY,
 OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
 ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE
 REQUIREMENTS OF FLORIDA STATUTES.
  
 2)107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS:
 OCCUPANCY TYPE
 MINIMUM BUILDING TYPE
 FIRE SPREINKLERED OR NOT
 FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
 PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS
 AND OR CEILINGS MORE THAN 1STORY?
  
 3) NOTE # 3 SCOPE OF WORK NOTE # 3 INDICATES THE
 REMOVAL OF ACOUSTICAL CEILINGS AND THEN FRAMING IN NEW
 AND HANGING DRYWALL CEILINGS AS REQUIRED BY CODE. NO
 PLANS WERE SUPPLIED TO BE ABLE TO COMPLETE A REVIEW
 WITH. NO MATERIALS, SPANS, NO INFORMATION. 107.3.5.1.1
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. 2014 FBC-B
 TABLE 2508.1 ASTM C754; ASTM C1007, GA 216 & ASTM C840.
 PLANS WILL NEED TO IDENTIFY THE DEFLECTION LIMITATION,
 ALLOWABLE CEILING SPAN FOR TYPE OF FRAMING MEMBER,
 IDENTIFY FRAMING MEMBERS, WILL THEY NEED STIFF BACKS,
 GAUGE OF FRAMING MEMBERS, CENTERS OF FRAMING MEMBERS,
 THE THICKNESS OF DRYWALL, ATTACHMENT, TYPE OF FASTENER,
 SPACING, GAUGE OF FASTENER AND LENGTH OF FASTENER.
  
 NOTE DEPENDING ON THE A/C DUCTWORK LAYOUT, MAY REQUIRE
 FIRE DAMPERS AND ACCESSIBLE PANELS.
  
 4) NOTE # 4 ADD ADDITIONAL STUDS TO SHOWER AREAS AS
 REQUIRED BY CODE. PLEASE PROVIDE THE SPACING OF STUDS,
 TYPE OF MATERIALS USED, FOR TYPE OF BUILDING,
 AND COMPLIANCE WITH 2014 FBC-B 2509.2 BASE FOR TILE.
 NOTE: 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, SUCH
 INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 5) NOTE # 5. HHANG DEN-SHIED OR EQUAL. 2014 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION, SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 6) NOTE # 9 INDICATES INSULATE FRAMED CEILING SPACES OF
 GUEST ROOMS WITH R-30 BATT MATERIALS. PLEASE SHOW
 COMPLIANCE WITH 2014 FBC-ENERGY C402.4.9.2 UNVENTED
 DROPPED CEILING CAVITIES.
 WHERE UNVENTED DROPPED CEILING CAVITIES OCCUR OVER
 CONDITIONED SPACES THAT DO NOT HAVE AN AIR BARRIER
 BETWEEN THE CONDITIONED AND UNCONDITIONED SPACE (SUCH
 AS T-BAR CEILINGS), THEY SHALL BE COMPLETELY SEALED
 FROM THE EXTERIOR ENVIRONMENT (AT THE ROOF PLANE) AND
 ADJACENT SPACES BY A CONTINUOUS AIR BARRIER THAT IS
 ALSO SEALED TO THE AIR BARRIER OF THE WALLS. IN THAT
 CASE, THE ROOF ASSEMBLY SHALL CONSTITUTE BOTH THE UPPER
 THERMAL ENVELOPE AND PRESSURE ENVELOPE OF THE BUILDING.
  
  
 6) NOTE # 12 INDICATE TO INSTALL EXIT AND EMERGENCY
 LIGHTING AS REQUIRED. PLEASE PROVIDE A LIFE SAFETY
 PLAN.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS:
 OCCUPANCY TYPE
 MINIMUM BUILDING TYPE
 FIRE SPREINKLERED OR NOT
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 EMERGENCY LIGHTING
 DERECTIONAL EXIT LIGHTS
 EXIT LIGHTS
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  