Plan Review Notes For Permit 15080077 |
Permit Number |
15080077 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-08-20 05:32:59 | 1) THIS PROJECT IS CONSIDERED A CHANGE OF OCCUPANCY IN | | ACCORDANCE WITH 2014 FBC-SEC.308.6 AND SHALL COMPLY | | WITH ALL REQUIREMENTS OF THE NEW OCCUPANCY PER 2014 | | FBC-EXISTING BUILDING SEC.1001.3 & 1010. | | 2) SUBMIT THE TOTAL OCCUPANT LOAD AND AGES OF THE | | OCCUPANTS AND DAYS AND HOURS OF OPERATION. FBC -B | | SEC.308.6. | | 3) THE MINIMUM NUMBER OF SANITARY FACILITIES SHALL | | COMPLY WITH TABLE 403.1 OF 2014 FBC-PLUMBING FOR THE | | TYPE AND NUMBER OF FIXTURES NEEDED FOR THE DAY CARE | | OCCUOANCY. | | 4) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR ALL | | CHANGES TO THE PLUMBING SYSTEM REQUIRED BY THE CHANGE | | OF OCCCUPANCY REQUIREMENTS. WPB AMEND. TO FBC SEC. | | 107.2.1. | | 5) THE CHANGE IN OCCUPANCY WILL TRIGGER COMPLIANCEQITH | | THE 2014 FBC- ACCESSIBILITY PER THE 2014 FBC-EXISTING | | BUILDING SEC 1006.1. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|