Plan Review Notes
Plan Review Notes For Permit 15080077
Permit Number 15080077
Review Stop M
Sequence Number 1
Notes
Date Text
2015-08-19 09:15:051ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080077
 8/19/15
  
 1) A COMPLETE REVIEW OF THE PROPOSED DAY CARE OCCUPANCY
 CANNOT BE ACCOMPLISHED UNTIL THE PLANS HAVE BEEN
 REVISED IN ACCORDANCE WITH BUILDING PLAN REVIEW
 COMMENTS (JWITMER- 8/8/15). PLEASE SUBMIT CORRECTED
 PLANS FOR REVIEW.
 2) REFER TO SECTION 1009.1 FBC-14 EXISTING BUILDING
 CODE AND PROVIDE VENTILATION CALCULATIONS FOR ALL
 PROPOSED ROOMS AND SPACES IN ACCORDANCE WITH TABLE
 403.3 FBC-14 MECHANICAL. PROVIDE A SCHEDULE ON THE PLAN
 INDICATING THE REQUIRED AMOUNT CFM'S OF OUTSIDE AIR,
 AND THE AMOUNT OF CFM'S BEING PROVIDED BY THE EXISTING
 SYSTEM(S). REVISE THE PLANS TRO SHOW ANY REQUIRED
 ALTERATIONS OR MODIFICATIONS TO THE EXISTING SYSTEM(S)
 TO ACCOMODATE THE NEW OCCUPANCY.
 3.A) REFER TO SECTION 466.7 FBC-14 BUILDING: DETECTION
 AND ALARM SYSTEMS.
 DAY CARE OCCUPANCIES SHALL BE PROVIDED WITH A FIRE
 ALARM SYSTEM IN ACCORDANCE WITH SECTION 907 AND THIS
 SECTION.
 3.B) REFER TO SECTION 466.7.2 DETECTION.
 A SMOKE DETECTION SYSTEM SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 72, WITH PLACEMENT OF DETECTORS IN
 EACH STORY IN FRONT OF DOORS TO THE STAIRWAYS AND IN
 THE CORRIDORS OF ALL FLOORS OCCUPIED BY THE DAY CARE
 OCCUPANCY. DETECTORS ALSO SHALL BE INSTALLED IN
 LOUNGES, RECREATION AREAS AND SLEEPING ROOMS IN THE DAY
 CARE OCCUPANCY.
  
 PLEASE NOTE THAT MEETING COMPLIANCE WITH THE ABOVE
 SECTIONS WILL REQUIRE ANY NEW OR EXISTING DUCT SMOKE
 DETECTORS, FIRE DAMPERS, OR SMOKE DAMPERS TO BE LINKED
 WITH THE ALARM SYSTEM.
 4) PLEASE PROVIDE A RESPONSE NARRATIVE TO ALL BUILDING
 DEPARTMENT COMMENTS FROM THE DESIGN PROFESSIONAL OF
 RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER