2015-08-19 09:15:05 | 1ST REVIEW: FBC 2014 MECHANICAL |
| PERMIT #15080077 |
| 8/19/15 |
| |
| 1) A COMPLETE REVIEW OF THE PROPOSED DAY CARE OCCUPANCY |
| CANNOT BE ACCOMPLISHED UNTIL THE PLANS HAVE BEEN |
| REVISED IN ACCORDANCE WITH BUILDING PLAN REVIEW |
| COMMENTS (JWITMER- 8/8/15). PLEASE SUBMIT CORRECTED |
| PLANS FOR REVIEW. |
| 2) REFER TO SECTION 1009.1 FBC-14 EXISTING BUILDING |
| CODE AND PROVIDE VENTILATION CALCULATIONS FOR ALL |
| PROPOSED ROOMS AND SPACES IN ACCORDANCE WITH TABLE |
| 403.3 FBC-14 MECHANICAL. PROVIDE A SCHEDULE ON THE PLAN |
| INDICATING THE REQUIRED AMOUNT CFM'S OF OUTSIDE AIR, |
| AND THE AMOUNT OF CFM'S BEING PROVIDED BY THE EXISTING |
| SYSTEM(S). REVISE THE PLANS TRO SHOW ANY REQUIRED |
| ALTERATIONS OR MODIFICATIONS TO THE EXISTING SYSTEM(S) |
| TO ACCOMODATE THE NEW OCCUPANCY. |
| 3.A) REFER TO SECTION 466.7 FBC-14 BUILDING: DETECTION |
| AND ALARM SYSTEMS. |
| DAY CARE OCCUPANCIES SHALL BE PROVIDED WITH A FIRE |
| ALARM SYSTEM IN ACCORDANCE WITH SECTION 907 AND THIS |
| SECTION. |
| 3.B) REFER TO SECTION 466.7.2 DETECTION. |
| A SMOKE DETECTION SYSTEM SHALL BE INSTALLED IN |
| ACCORDANCE WITH NFPA 72, WITH PLACEMENT OF DETECTORS IN |
| EACH STORY IN FRONT OF DOORS TO THE STAIRWAYS AND IN |
| THE CORRIDORS OF ALL FLOORS OCCUPIED BY THE DAY CARE |
| OCCUPANCY. DETECTORS ALSO SHALL BE INSTALLED IN |
| LOUNGES, RECREATION AREAS AND SLEEPING ROOMS IN THE DAY |
| CARE OCCUPANCY. |
| |
| PLEASE NOTE THAT MEETING COMPLIANCE WITH THE ABOVE |
| SECTIONS WILL REQUIRE ANY NEW OR EXISTING DUCT SMOKE |
| DETECTORS, FIRE DAMPERS, OR SMOKE DAMPERS TO BE LINKED |
| WITH THE ALARM SYSTEM. |
| 4) PLEASE PROVIDE A RESPONSE NARRATIVE TO ALL BUILDING |
| DEPARTMENT COMMENTS FROM THE DESIGN PROFESSIONAL OF |
| RECORD. |
| |