Date |
Text |
2015-08-06 13:18:49 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| THERE IS INSUFFICIENT INFORMATION PROVIDED TO DETERMINE |
| OR APPROVE THE OCCUPANCY USE CHANGES. |
| |
| 1. NEW DAY CARE OCCUPANCIES SHALL COMPLY WITH FLORIDA |
| STATUTE CHAPTER 402, NFPA 1 CHAPTER 20.3 AND NFPA 101 |
| CHAPTER 16. |
| |
| 2. PROVIDE DETAILED INFORMATION REGARDING THE INTENT OF |
| THE OCCUPANCY. PER NFPA 1 AND 101, OCCUPACIES THAT |
| INCLUDE PART-DAY PRESCHOOLS, KINDERGARTENS, AND OTHER |
| SCHOOLS WHOSE PURPOSE IS PRIMARILY EDUCATION, EVEN |
| THOUGH THE CHILDREN WHO ATTEND SUCH SCHOOLS ARE OF |
| PRESCHOOL AGE, SHALL COMPLY WITH THE PROVISION OF |
| CHAPTER 14, NEW EDUCATIONAL OCCUPACIES. |
| |
| 2. A LIFE SAFETY PLAN IS NOT INCLUDED AND SHALL BE |
| PROVIDED INCLUDING OCCUPANCY LOADS, FIRE ALARM/FIRE |
| SPRINKLER DETAILS, EXIT SIGNS, EMERGENCY LIGHTS, |
| MAXIMUM TRAVEL DISTANCE, MAXIMUM COMMON PATH OF TRAVEL, |
| FIRE EXTINGUISHERS LOCATIONS, ETC. |
| |
| 3. A MONITORED FIRE ALARM SYSTEM IS REQUIRED. |
| |
| 4. PROVIDE DETAILS FOR COMPLYING WITH THE PROVISIONS OF |
| NFPA 101 16.2.11.1.1, WINDOWS FOR RESCUE. |
| |
| 5. PROVIDE DETAILS OF ALL EXITS THAT LEAD TO A PUBLIC |
| WAY INCLUDING THOSE LEADING TO EXTERIOR GATES AND |
| EXITING THROUGH THOSE GATES TO A PUBLIC WAY. |
| |
| 6. PROVIDE DETAILS REGARDING THE SECOND FLOOR AND |
| LIMITING OR CONTROLLING ACCESS. ADDITIONALLY, ENSURE |
| EGRESS FROM THE SECOND FLOOR SHOULD OCCUPANCY OCCUR. |
| |
| 7. ADDITIONAL COMMENTS OR CONCERNS MAY BE PROVIDED |
| BASED ON THE SUBMITTAL OF THE ABOVE INFORMATION. |