2015-11-17 11:28:202ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080007
 11/17/15
  
 1) THE SUBMITTED ENERGY GAUGE SOFTWARE CALCULATION FORM
 506-2010 IS OUTDATED- SECTION C101.5.1 FBC-14 ENERGY
 CONSERVATION. PLEASE PROVIDE TWO CALCULATION FORMS
 USING THE UPDATED 2014 VERSION OF THE PROGRAM.
 2) PLEASE INDICATE THE R-VALUE OF THE DUCT INSULATION
 ON THE PLANS- TABLE C403.2.7.1.
  