Plan Review Notes
Plan Review Notes For Permit 15080007
Permit Number 15080007
Review Stop M
Sequence Number 1
Notes
Date Text
2015-08-07 14:34:341ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15080007
 8/7/15
  
 1) REFERENCE SECTION C403.2.2 FBC-14 ENERGY
 CONSERVATION: PROVIDE COOLING AND HEATING LOAD
 CALCULATIONS FOR THE NEW AC SYSTEMS IN ACCORDANCE WITH
 ACCA MANUAL N OR THE ACCA/ASHRAE STANDARD 183.
 2) REFERENCE SECTION C101.3 FBC-14 ENERGY CONSERVATION:
 THE PROPOSED PROJECT SHALL BE IN COMPLIANCE WITH
 CHAPTER 4 FBC-14 ENERGY CONSERVATION. PLEASE SUBMIT TWO
 COMPLETED EFFICIENCY COMPLIANCE FORMS USING FLORIDA
 BUILDING COMMISSION SOFTWARE.
 3) SHEET M-3: PROVIDE UPDATED VENTILATION CALCULATIONS
 USING EITHER TABLE 403.3 FBC-14 MECHANICAL, OR ASHRAE
 62- 2010. PROVIDE A SCHEDULE ON THE PLAN THAT INDICATES
 THE REQUIRED O/A CFM'S AND THE PROVIDED O/A CFM'S.
 4) SHEET M-5: THE DUCT SMOKE DETECTOR SHALL BE LOCATED
 IN THE RETURN AIR DUCT- SECTION 606.2.1 FBC-14
 MECHANICAL.
 5) PROVIDE TWO COPIES OF A FLORIDA PRODUCT APPROVAL OR
 MIAMI-DADE NOA FOR THE GREENHECK LOUVERS PER FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/
 2010.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  