2015-09-30 14:18:15PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE
 ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH
 REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE
 REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED
 SHALL BE RESUBMITTED FOR ANOTHER REVIEW.
  
 1. FIRE ALARM WORK SHALL BE UNDER A STAND-ALONE FIRE
 ALARM PERMIT.
 2. WAREHOUSE 101- MISSING AN EXIT LIGHT AT THE E. SIDE
 EXIT.
 3. WAREHOUSE 101- DOES NOT APPEAR TO HAVE ENOUGH
 EMERGENCY ILLUMINATION.
 4. BREAK ROOM 103- MISSING AN EMERGENCY LIGHT BY THE S.
 END, (OPERATIONS)
 5. MECH ROOM 107- MISSING AN EMERGENCY LIGHT.
 6. MECH ROOM 107- MISSING THE SERVICE OUTLET REQUIRED
 BY NEC 210.63
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  
 RETURNED TO BIN FOR FURTHER REVIEWS. MA
  