Plan Review Notes For Permit 15080007 |
Permit Number |
15080007 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2015-09-30 14:18:15 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS | | EXAMINER HAVE COMPLETED THE ELECTRICAL REVIEW OF THE | | ABOVE MENTIONED JOB. BELOW ARE THE COMMENTS WITH | | REGARDS TO THE REQUIRED CORRECTIONS. THE PLANS SHALL BE | | REVISED TO ADDRESS FOLLOWING ITEMS; ONCE CORRECTED | | SHALL BE RESUBMITTED FOR ANOTHER REVIEW. | | | | 1. FIRE ALARM WORK SHALL BE UNDER A STAND-ALONE FIRE | | ALARM PERMIT. | | 2. WAREHOUSE 101- MISSING AN EXIT LIGHT AT THE E. SIDE | | EXIT. | | 3. WAREHOUSE 101- DOES NOT APPEAR TO HAVE ENOUGH | | EMERGENCY ILLUMINATION. | | 4. BREAK ROOM 103- MISSING AN EMERGENCY LIGHT BY THE S. | | END, (OPERATIONS) | | 5. MECH ROOM 107- MISSING AN EMERGENCY LIGHT. | | 6. MECH ROOM 107- MISSING THE SERVICE OUTLET REQUIRED | | BY NEC 210.63 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE | | PREVIOUSLY REVIEWED SHEETS. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU | | | | RETURNED TO BIN FOR FURTHER REVIEWS. MA | | |
|